Step 3 — defrost control, Quiet shift, Defrost – Carrier PERFORMANCE 50VT-A User Manual

Page 20: 50v t -- a, Fig. 16 -- interface fan board (ifb)

Advertising
background image

20

HIGH

LOW

COM

QC5

QC4

QC3

KZ

KL

07

09

08

0L0

ALO

R13 C8

R11

Q1

Q3

D2

AL2

DCR

QCR

QC1

C

RL

01

G1

G2

Z1

A7

R9

AB A15

C4

C9

C0

QIL

Z2

06

04

U1

C3

R4

RL4

JWZ

C7

D5

D3

R3 R5

R6

R2

JW5

QCB

Y

R

W2 Y

C

W3 W3 W2 W2 C

JW4

P2

JW3

P4

P1

W2

W3

Y2

Y1

Y

DH

G

C

R

SSTZ-8

P3

SDL

24V

A

C/R

3AMP

CDM/C

F1

STD

DEHUM

A09059

Fig. 16 -- Interface Fan Board (IFB)

COMPRESSOR

ACCUMULATOR

OUTDOOR COIL

INDOOR COIL

LCS

LEGEND

HPS – High Pressure Switch

LCS – Loss of Charge Switch

Accurater

®

Metering De vice

Arrow indicates direction of flo

w

Position

HP S

TXV in Bypass

Metering
Position

C03012

Fig. 17 -- Typical Heat Pump Operation, Heating Mode

Step 3 — Defrost Control

Quiet Shift

Quiet Shift is a field--selectable defrost mode, which will eliminate

occasional noise that could be heard at the start of defrost cycle and
restarting of heating cycle. It is selected by placing DIP switch 3

(on defrost board) in ON position.
When Quiet Shift switch is placed in ON position, and a defrost is

initiated, the following sequence of operation will occur. Reversing
valve will energize, outdoor fan will turn off, compressor will turn

off for 30 sec and then turn back on to complete defrost. At the

start of heating after conclusion of defrost reversing valve will
de--energize, compressor will turn off for another 30 sec, and the

outdoor fan will stay off for 40 sec, before starting in the Heating
mode.

Defrost

The defrost control is a time/temperature control which includes a

field--selectable time period (DIP switch 1 and 2 on the board)
between defrost cycles of 30, 60, 90, or 120 minutes (factory set at

60 minutes). To initiate a forced defrost, two options are available

depending on the status of the defrost thermostat.

If defrost thermostat is closed, speed--up pins (J1) must be shorted
by placing a flat head screw driver in between for 5 sec and

releasing, to observe a complete defrost cycle. When the Quiet
Shift switch is selected, compressor will be turned off for two 30

sec intervals during this complete defrost cycle, as explained

previously. When Quiet Shift switch is in factory default OFF
position, a normal and complete defrost cycle will be observed.
If defrost thermostat is in open position, and speedup pins are
shorted (with a flat head screw driver) for 5 sec and released, a

short defrost cycle will be observed (actual length is dependent

upon the selected Quiet Shift position). When Quiet Shift switch is
in ON position, the length of defrost is 1 minute (30 sec

compressor off period followed by 30 sec of defrost with
compressor operation). On return to heating operation, compressor

will again turn off for an additional 30 sec and the outdoor fan for

40 sec. When the Quiet Shift is in OFF position, only a brief 30
sec. cycle will be observed.
NOTE: Unit will remain in defrost until defrost thermostat
reopens at approximately 65_F (18_C) coil temperature at liquid
line or remainder of defrost cycle time.