Cub Cadet Z-Force S Series User Manual

Page 111

Advertising
background image

Electrical System

105

5d.

Interpretation:

•

If the stator fails either or both tests, it is likely to be bad.

•

If the stator fails the out put test, but passes the resistance test, there is a possibility that the magnets on
the rotor (flywheel) have lost their fields. This is theoretically possible, but extremely rare in practice.

•

It is necessary to remove the flywheel to test the magnets. If the magnets inside the flywheel will draw a
steel screwdriver to them, they are good. If not, the flywheel must be replaced.

6.

Regulator/rectifier check: See Figure 7.26.

6a.

Check the ground.

•

With the engine running and the stator leads re-
connected to the regulator/rectifier, perform a
ground-side voltage-drop test from the regula-
tor/rectifier to the engine block.

•

If the voltage reading is greater than 0.1 Volts
D.C., replace or properly fasten the ground wire
that connects the regulator/rectifier to the
engine block. Retest to confirm good connec-
tion.

6b.

Bench Test: See Figure 7.27.

•

Set a digital multi-meter to read on the X100

Ω

scale.

•

With the key OFF and the fuse removed, unplug
all the wires from the regulator/rectifier.

•

Remove the regulator/rectifier from the engine
(not strictly necessary, but provides easy
access).

•

Make the resistance tests described in the
accompanying table.

•

B+ is the D.C. terminal

•

A.C.1 is the A.C. terminal nearest B+

•

A.C.2 is the A.C. terminal furthest from B+

Figure 7.26

Figure 7.27

A.C.2 A.C.1 B+

Advertising