Appendix A

FA464DR Receiver Parameters

Default

Active

on

Output Condition

Options for each output

1

Alarm

ALARM / ALARM+TAMPER / TAMPER /

2

Alarm

LO BATT / INACTIVE / TAMP+LO BATT /

3

Alarm

TAMP+INACTIVE / LO BATT+INACTIVE /

4

Alarm

ANY TX FAULT / DISABLED

...
...

16

Alarm


Transmitter Default

Condition Mode

Alarm

Follower

FOLLOWER / MOMENTARY / LATCHING

Inactive

Follower

"

Tamper

Latching

"

Low

Batt

Latching

"

Default Momentary Output time: 4 seconds

1 - 16 seconds

Default Receiver Parameters:

System ID:

(randomly assigned at factory)

0 - 255

Point supervision:

Yes

Yes / No

Supervision window*:

4 hours

1 - 99 minutes, 2 - 99 hours

(Note: use 60 minutes for 1-hour window)

Access

code:

3446

0000 - 9999

Vision Plus compatible:

No

Yes / No


* Selecting appropriate Supervision Window values: Acceptable values for a supervision window permit

timely notification of inactive points but preclude false inactive reports.

A point is declared inactive as follows: The receiver looks for at least one supervisory transmission (or
"check-in") from each supervised transmitter during the period of time programmed as the supervisory
window. The first time the receiver gets a supervisory signal from a transmitter within a new window, it
considers the transmitter active for the remainder of the window. If it fails to get another signal in the
following supervisory window, it declares the point inactive at the end of the window.

The actual time between a transmitter becoming inactive and being reported inactive will range from slightly
more than the supervisory window value to slightly less than twice the window period. For example, the
default supervisory window is 4 hours. If a transmitter becomes inactive, the inactive fault output will be
triggered in 4 to 8 hours. There are many factors which can prevent individual check in transmissions from
reaching the receiver, so the greatest possible ratio of check-in signals to supervision window is desirable.
For example, typical default settings for Inovonics products include supervision windows of 4 hours and
transmitter check-in times at 60 seconds. In this case, the receiver has 240 "chances" to receive a check-in
transmission per supervision window period. Significantly decreasing this ratio increases the possibility that
the receiver will erroneously declare a point inactive.

When transmitters are set for 60-second check-in, a rule of thumb for setting the supervision window is to
allow at least one hour for each 16 transmitters in the system. Decreasing the supervision window to less
than one hour should only be done in consultation with Inovonics technical service.