Resetting outputs: All outputs can be reset either by pressing the Reset Button or by pulling the Reset

Input terminal to ground. This can be done by installing a switch between the reset input and the ground

terminal on the receiver. (NOTE: The distance to this switch must not exceed 25 feet). Remote or

automatic resetting can be accomplished by relay control from some hardwire panels. All outputs are

cleared. If a transmitter remains in alarm or if a fault condition is not corrected, the output will reactivate at

the next supervisory signal received from the transmitter.

16

RESE T

GND

14

3

13

4

PROGRA MME D

ACTIVATE D

TAMPE RED

LOW BATTE RY

INA CTIVE

TRA NSMITTER

PROGRA MMING

TRA NSMITTER

NUMBE R

DELETE

ADVANCE

TAMPE R

TA

M

P

E

R

15

1

NC

CO

M

NO

NO

CO

M

NC

NC

CO

M

NO

NO

CO

M

NC

NC

CO

M

NO

NO

CO

M

NC

NC

CO

M

NO

NO

CO

M

NC

2

REVIEW

STATUS

DC POWER ONLY

12VDC TYPICAL 18VDC MAX

+

Reset Circuit Example:

25’ maximum distance

Switch to Receiver

Figure 4

Deleting points: Transmitter programming information remains in non-volatile receiver memory.

Transmitters may be re-programmed using the current parameters.

1. Use

the

Advance Button to show the desired point on the Transmitter Number

Display.

2. Press

the

Delete Button on theFA464DRboard. A 3-tone signal will be heard. The

Programmed LED will change from steady "on" to flashing.

3. Points may also be deleted via the FA116 programmer.

Using the FA116 programmer keypad: Program all 64 points with FA116 programmer. Options which

may be programmed include end-of-line resistor, internal contact (widegap magnet), changing external

switch configuration, check-in time interval and desired output channel. In addition, receiver parameters

may be set also, including supervisory window. See

Restoring factory defaults: This sequence restores all factory defaults and clears all programmed points.

Note: This sequence resets the receiver access code to default value (3446).

1. Press and hold the Advance Button.
2. Press and release the Reset Button. A steady tone will begin.
3. Release

the

Advance Button. The Decode and Valid Decode LEDs will go

out.

4. Press and hold the Delete Button.
5. When a rapid "deedle- deedle- deedle" tone is heard and the Decode LED flashes,

release the Delete Button.