AAF International SAH User Manual

Page 10

Advertising
background image

10

Repeat the process of prefilter installation until all tracks are filled with

prefilters.

3.7 Gas-phase Chemical Filter Installation: The following

instructions are specific to the installation of the Type MD gas-phase

chemical filter cassettes into an SAH-XXX-2P-MD-2P-6F housing.

Unless specifically mentioned otherwise, the procedure for installing

the Type HD and Type CG cassettes will be exactly the same.

3.7.1 Preparing the Cassette for Installation: Remove the

cassette from its carton and plastic bag. You will notice that each

cassette or half-cassette is accompanied by a plastic bag

containing loose gaskets (see top right). These are supplied

specifically for use when the cassette is to be installed into an AAF

Side Access Housing. These gaskets are critical for the sealing of

the gas-phase cartridges to prevent by-pass of contaminated air

around the filters.

Step 2: Slide the prefilter in as far as it will go.

Step 3: The installed prefilter.

Type MD half-cassette with butterfly and

side gaskets.

Type HD half-cassette with butterfly and

side gaskets.

Install the gaskets onto the cassettes and half-cassettes. The following

pictures show the installation of gaskets onto a Type HD half-cassette.

The process will be similar for the Type MD and Type CG cassettes.

Side gaskets:

Step 1: Remove the paper strip on the back of the black gasket to expose the adhesive.

Step 2: Locate the gasket on the leaving air side of the half-cassette along the edge of

the cassette side plate. A gasket location guide has been formed into the side plate.

The gasket should be located to the outside of this line.

(Note the Type CG cassette is not shown.)

Advertising