The components shall be retained and stored in their protective packaging

until immediately prior to installation. Care shall be taken to ensure that the

packages are not dropped or subjected to any impact loads.
At all times the equipment shall be protected from exposure to weather.

The equipment shall be stored in a clean, dry, temperature-controlled

environment. All items shall be stored on pallets so that they are

elevated above grade. Side Access Housings (SAH) shall not be

stacked. Particulate and gas-phase filters, shall not be stacked more

than three (3) cartons high to prevent crushing. Only particulate filters

shall be stacked on particulate filters, and gas-phase filters on gas-phase

filters. The gas-phase filters ship inside a carton enclosed in transparent

protective plastic. Under no circumstances shall the filters be removed

from this plastic protection until immediately prior to installation.
Filter products shall not be stored in areas where they may become

contaminated by chemicals, either acids or alkali’s, in liquid, vapor or

gaseous form.

Side Access Housing, Model SAH-202-2P-MD-2P-6F, with

tracking to accommodate four (4) MD cassettes. Optional channel

base is included.

1.3 Product Descriptions

1.3.1 Side Access Housing (SAH): Each (SAH) will be received

individually mounted on a shipping pallet and wrapped in plastic for

protection during shipping. Depending on the size and complexity

of the SAH it may ship in sections on multiple pallets. Refer to the

product drawings submitted on the order for details. The SAH can

be supplied in three styles, Type MD, Type HD or Type CG,

depending on the style of SAAF Cassette gas-phase chemical filter

that it is intended to accommodate (see 1.3.2 for details). Different

internal support tracks and track spacings will be provided

depending on the type of cassette to be used.
Any particular filter system will normally be assembled using only

one type of cassette, Type MD, Type HD, or Type CG. Cassettes will

almost never be mixed in a single-filter system. Different types of

cassettes are not interchangeable within any particular filter bank.

1.3.2 Gas-phase Chemical Filter Cassettes: Gas-phase filter

cassettes are shipped in cartons and plastic bags. The carton shown

below contains a single 6" high x 24" wide x 18" deep Type MD

cassette which is supplied as two (2) 6" high x 12" wide x 18" deep

half cassettes.