CHAPTER 2
INSTALLATION

Page 20 of 166 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 PR1:10/18/12

Benchmark 1.5LN Low NOx Boiler

Installation, Operation and Maintenance Manual

GF-120

OMM-0041 0E

NATURAL

GAS

SUPPLY

DIRT

TRAP

1-1/2” MANUAL
GAS SHUTOFF

VALVE

GAS PRESSURE

REGULATOR

(REQUIRED FOR

MASSACHUSETTS

INSTALALTIONS

ONLY)

Figure 2-6: Manual Gas Shut-Off Valve Location

2.7.4

IRI Gas Train Kit

The IRI gas train is an optional gas train configuration which is required in some areas for code
compliance or for insurance purposes. The IRI gas train is factory pre-piped and wired. See
Appendix F, Drawing AP-A-830 for details.

2.8 AC ELECTRICAL POWER WIRING

The AERCO Benchmark 1.5 Electrical Power Wiring Guide, GF-4060, must be consulted prior
to connecting any AC power wiring to the unit. External AC power connections are made to the
unit inside the Power Box on the front panel of the unit. Remove the front door of the unit to
access the Power Box mounted directly above the Control Box. Loosen the four Power Box
cover screws and remove cover to access the AC terminal connections inside the Power Box
(Figure 2-7).

NOTE

All electrical conduit and hardware must be installed so that it
does not interfere with the removal of any unit covers, inhibit
service/maintenance, or prevent access between the unit and
walls or another unit.