CHAPTER 4

INITIAL START-UP

PR1: 10/18//12 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 Page 55 of 166


GF-120

OMM-0041 0E

Benchmark 1.5LN Low NOx Boiler

Installation, Operation and Maintenance Manual

The oxygen level at the 30% valve position should be as shown below. Also, ensure that

47.

the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.

Table 4-5: Combustion Oxygen Levels for a

30% Air/Fuel Valve Position

Oxygen

%

± 0.2

Carbon

Monoxide

NOx

7.0 %

<50 ppm

<30 ppm

If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼

48.

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.

Once the oxygen level is within the specified range at 30%, press the ENTER key to

49.

store the selected blower output voltage for the 30% valve position.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

50.

Press the CHANGE key. SET Valve Position will begin to flash.

51.

Press the ▼ arrow key until the SET Valve Position reads 16%, then press the ENTER

52.

key.

Press the ▼ arrow key until CAL Voltage 16% is displayed.

53.

Press the CHANGE key. CAL Voltage 16% will begin to flash.

54.

The oxygen level at the 16% valve position should be as shown below. Also, ensure that

55.

the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.

Table 4-6: Combustion Oxygen Levels for a

16% Air/Fuel Valve Position

Oxygen

%

± 0.2

Carbon

Monoxide

NOx

8.0 %

<50 ppm

<30 ppm

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼

56.

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.

Once the oxygen level is within the specified range at 16%, press the ENTER key to

57.

store the selected blower output voltage for the 16% valve position.

This completes the natural gas combustion calibration procedure.

58.