2 igniter-injector – AERCO BMK 1.5 LN October 2012 User Manual

Page 80

Advertising
background image



CHAPTER 7

MAINTENANCE

Page 80 of 166 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 PR1:10/18/12

Benchmark 1.5LN Low NOx Boiler

Installation, Operation and Maintenance Manual

GF-120

OMM-0041 0E

7.2 IGNITER-INJECTOR

The igniter-injector (part no. 58023) is located on the burner plate at the top of the boiler. In
addition to providing the ignition spark required to light the burner, the igniter-injector also
contains a gas injector tube which connects to the staged ignition assembly. Figure 7-1 shows
the complete burner assembly removed from the boiler and indicates the location of the igniter-
injector flame detector and other related components.

The igniter-injector may be hot, therefore, care should be exercised to avoid burns. It is easier to
remove the igniter-injector from the unit after the unit has cooled to room temperature.

AIR/FUEL

VALVE

STAGED

IGNITION

ASSEMBLY

FLAME
DETECTOR

IGNITOR-

INJECTOR

BLOWER

BURNER

PLATE

BURNER

Figure 7-1: Benchmark 1.5LN Burner Assembly (Shown Removed from Boiler)

To inspect/replace the Igniter:

Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power

1.

from the unit

Remove the side and top panels from the unit.

2.

Disconnect the cable from the igniter-injector (Figure 7-1).

3.

Refer to the partial exploded view in Figure 7-2. Using a 7/16” open-end wrench,

4.

disconnect the compression nut securing the gas injector tube of the igniter-injector to
the elbow of the staged ignition assembly. Disconnect the staged ignition assembly from
the igniter-injector.