CHAPTER 4
INITIAL START-UP
PR1: 10/18//12 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 Page 59 of 166
GF-120
OMM-0041 0E
Benchmark 1.5LN Low NOx Boiler
Installation, Operation and Maintenance Manual
5.
Once the desired over-temperature alarm setting (210ºF) is displayed, press the SET button
to store the setting in memory.
6.
To calibrate the offset (P1), press and hold the SET button for 8 seconds on the Digital
Alarm Switch. Access code value 0 should appear in the display. The switch comes from the
factory with the code set at 0. AERCO recommends that you do not change this code.
7.
Press the SET button again to enter the code. The first parameter label (SP) will appear in
the display.
8.
Usi
ng the ▲ and ▼ arrow keys, select parameter P1.
9.
Press SET to view the value stored in memory.
10.
If the desired value is not displayed, modify the setting using the ▲ and ▼ arrow keys. The
value can be changed from -10° to +10° offset. Press SET to enter the value and exit to the
text parameter.
11.
To exit the programming mode, press the SET
and ▼ buttons simultaneously, or simply wait
one minute and the display will automatically exit the programming mode.
12.
Once the programming mode has been exited, the display will show the current outlet water
temperature of the boiler.