CONTROL PANEL OPERATING PROCEDURES

1. The

DEMAND

LED status indicator will light.

2. The unit checks to ensure that the Proof of

Closure (POC) switch in the downstream
Safety Shut-Off Valve (SSOV) is closed.
See Figure 3-3 for SSOV location.

TO AIR/FUEL

VALVE

SSOV

GAS

INLET

MANUAL

SHUT-OFF

VALVE

Figure 3-3.

SSOV Location

3. With all required safety device switches

closed, a purge cycle will be initiated and the
following events will occur:

(a) The Blower relay energizes and turns

on blower.

(b) The Air/Fuel Valve rotates to the full-

open purge position and closes purge
position switch. The dial on the Air/Fuel
Valve (Figure 3-4) will read 100 to
indicate that it is full-open (100%).

(c) The VALVE POSITION bargraph will

show 100%.

4. Next, the blower proof switch on the Air/Fuel

Valve (Figure 3-5) closes. The display will
show Purging and indicate the elapsed time
of the purge cycle in seconds. The normal
(default) time for the purge cycle is 7
seconds.

5. Upon completion of the purge cycle, the

Control Box initiates an ignition cycle and
the following events occur:

(a) The Air/Fuel Valve rotates to the low-

fire ignition position and closes the
ignition switch. The dial on the Air/Fuel
Valve (Figure 3-6) will read between 25
and 35 to indicate that the valve is in
the low-fire position.

(b) The igniter relay is activated and

provides ignition spark.

(c) The gas Safety Shut-Off Valve (SSOV)

is energized (opened) allowing gas to
flow into the Air/Fuel Valve.

Figure 3-4.

Air/Fuel Valve In Purge Position

Figure 3-5.

Blower Proof Switch

3-9