SAFETY DEVICE TESTING

5. Re-enable the blower output drive voltage

by performing the following steps:

(a) Press the MENU key until CONFIGUR-

ATION MENU

is displayed.

(b) Press

the

▲ arrow key until the ANA-

LOG OUTPUT

function is displayed,

then press the CHANGE key.

(c) Press

the

▲ arrow key until VALVE

POSITION 0-10V

is displayed, then

press the ENTER key.

6. Once the unit has proved flame, turn off the

blower by going to the Configuration Menu,
Analog Output

menu item and select OFF.

7. The Blower Proof Switch will open and the

blower should stop. The unit should shut
down and display AIRFLOW FAULT
DURING RUN

.

8. Go to the Configuration Menu, Analog

Output

item and select VALVE POSITION 0-

10v

.

9.

Press the CLEAR button. The unit should

restart.

10. Next, check the Blocked Inlet Switch by first

noting the current position of the Iris Air
Damper and then closing the Damper to
position 8.

11. .The unit should shut down and again

display AIRFLOW FAULT DURING RUN.

12. Return the Iris Air Damper to its previous

setting.

13. Press the CLEAR button. The unit should

restart.

6.9 SSOV PROOF OF CLOSURE SWITCH

The SSOV shown in Figure 6-1 contains the
proof of closure switch. The proof of closure
switch circuit is checked as follows:

1. Set the unit’s ON/OFF switch to the OFF

position.

2. Place the unit in Manual Mode and set the

valve position between 25% and 30%

3. Refer to Figure 6-1 and locate the SSOV.

4. Remove the cover from the SSOV by

loosening the screw shown in Figure 6-4. Lift
off the cover to access the terminal wiring
connections.

5. Disconnect wire #148 from the SSOV to

“open” the proof of closure switch circuit.

6. The unit should fault and display SSOV

SWITCH OPEN.

7. Replace wire #148 and press the CLEAR

button.

8. Set the ON/OFF switch to ON to start the

unit.

9. Remove the wire again when the unit

reaches the purge cycle and PURGING is
displayed.

10. The unit should shut down and display

SSOV FAULT DURING PURGE.

11. Replace the wire on the SSOV and press

the CLEAR button. The unit should restart.

ACTUATOR

COVER

SCREW

SSOV

ACTUATOR

COVER

Figure 6-4

SSOV Actuator Cover Location

6.10 PURGE SWITCH OPEN DURING
PURGE

The Purge Switch (and Ignition Switch) is
located on the Air/Fuel Valve. To check the
switch, proceed as follows:

1. Set the unit’s ON/OFF switch to the OFF

position. Place the unit in manual mode and
set the valve position between 25% and
30%.

2. Remove the Air/Fuel Valve cover by rotating

the cover counterclockwise to unlock it and
then lift up (see Figure 6-5).

3. Remove one of the two wires (#171 or #172)

from the Purge Switch (Figure 6-6).

4. Initiate a unit start sequence.

6-5