Initial start-up – AERCO BMK 2.0 LN Nat. Gas June 2010 User Manual

Page 37

Advertising
background image

INITIAL START-UP

gas pressure adjustment screw (Figure 4-3).
Make gas regulator adjustments using a flat-
tip screwdriver to obtain 2.8” W.C.

BRASS HEX

HEAD CAP

(REMOVE TO

ACCESS GAS

PRESSURE

ADJUSTMENT

SCREW)

SSOV ACTUATOR

Figure 4-3

Gas Pressure Adjustment Screw

Location

11. Increase the valve position to 100% and

verify that the gas pressure downstream of
the SSOV remains at 2.8” W.C. Readjust
pressure if necessary.

12. With the valve position at 100%, insert the

combustion analyzer probe into the flue
probe opening and allow enough time for the
combustion analyzer to settle.

13. Compare the measured oxygen level to the

oxygen range for the inlet air temperature
shown in Table 4-1. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide
(NOx) readings do not exceed the values
shown.

Table 4-1

Combustion Oxygen Levels for a 100%

Valve Position

Inlet Air

Temp

Oxygen %

± 0.2

Carbon

Monoxide

NOx

>100°F

4.8 %

<100 ppm

<30 ppm

90°F

5.0 %

<100 ppm

<30 ppm

80°F

5.2 %

<100 ppm

<30 ppm

<70°F

5.3 %

<100 ppm

<30 ppm





14. If necessary, adjust the iris air damper

shown in Figure 4-4 until the oxygen level is
within the range specified in Table 4-1.

15. Once the oxygen level is within the specified

range at 100%, lower the valve position to
80%.

AIR

INLET

IRIS AIR

DAMPER

(SEE VIEW “A”)

USE 1/2"

WRENCH TO

INCREASE (CW)

OR DECREASE

(CCW) INLET AIR

IRIS ADJUSTMENT

VIEW A - A

Figure 4-4

Iris Air Damper Location/Adjustment

NOTE

The remaining combustion calibration
steps are performed using the
Combustion Cal Menu

included in the C-

More Control System. The combustion
calibration control functions will be used
to adjust the oxygen level (%) at valve
positions of 80%, 60%, 45%, 30% and
18% as described in the following steps.
These steps assume that the inlet air
temperature is within the range of 50°F to
100°F.

4-3