7 condensate trap, Maintenance, Figure 7-5 burner assembly exploded view – AERCO BMK 2.0 LN Nat. Gas June 2010 User Manual

Page 61: Figure 7-6 condensate trap

Advertising
background image

MAINTENANCE

BLOWER

PROOF

SWITCH

BLOCKED

INLET

SWITCH

AIR/FUEL

VAVLE

STAGED

IGNITION

ASSEMBLY

FLAME
DETECTOR

BURNER

PLATE

HEX NUTS &

WASHERS (6)

BLOWER

GASKET

IGNITOR-

INJECTOR

BURNER

BLOWER

BURNER

GASKET

BURNER

GASKET

Figure 7-5

Burner Assembly Exploded View

15. Remove the blower and air/fuel valve from

the burner plate by lifting straight up. Also,
remove the blower gasket which will be
replaced with a new gasket.

16. Remove the eight (8) 3/8-16 nuts from the

burner flange (Figure 7-4) using a 9/16”
wrench.

NOTE

The burner assembly is heavy, weighing
approximately 30 pounds.

17. Remove the burner assembly from burner

flange by pulling straight up.

18. Remove and replace the two (2) burner

gaskets.

NOTE

During reassembly, apply high-tempera-
ture, anti-seize lubricant to the threads of
the ignitor-injector and grounding screw.
Also, ensure that the ignitor-injector is
properly positioned as shown in Figure
7-3. Torque the ignitor-injector to 15 ft-lbs.

19.

Beginning with the burner assembly
removed in step 17, reinstall all the
components in the reverse order that they
were removed. During reassembly, replace
the gaskets for the blower and flame
detector with new parts.

20. Make sure to align the ignitor-injector and

flame detector tapped holes in the burner
plate with the heat exchanger top head.

21. Check to ensure that the grounding screw is

reinstalled.

7.7 CONDENSATE TRAP

The Benchmark 2.0LN Boiler contains a
condensate trap as shown in Figure 2-5. The
trap is located external to the unit and attached
to the condensate drain port on the exhaust
manifold. This trap should be inspected and, if
necessary, cleaned to ensure proper operation.
To inspect and clean the trap, refer to Figure 7-6
and proceed as follows:

1. Disconnect the condensate trap by

loosening the connections between the trap
and the exhaust manifold drain.

2. Remove the connections on the inlet and

outlet sides of the condensate trap (Figure
7-6).


FLOAT

THUMB

SCREWS

(4)

3/4 NPT

PORT

INLET

OUTLET

3/4 NPT

PORT

COVER

O-RING

ORIFICE
GASKET

Figure 7-6

Condensate Trap


3. Loosen the four (4) thumbscrews securing

the cover on the condensate trap. Remove
the cover.

7-5

Advertising