INITIAL START-UP

Combustion Oxygen Level at

60% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

5.5 %

<150 ppm

<100 ppm

26. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
down ▼ arrow key decreases the oxygen
level.

27. Once the oxygen level is within the specified

range at 60%, press the ENTER key to store
the selected blower output voltage for 60%
valve position

NOTE

The remaining steps basically repeat the
procedures in steps 20 through 27 for
valve positions of 45%, 30% and 18%.
However, since oxygen levels vary, these
steps are repeated in their entirety. When
performing these steps, also ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown for each valve position.

28. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

29. Press the CHANGE key. SET Valve Position

will begin to flash.

30. Press the ▼ arrow key until the SET Valve

Position

reads 45% and press the ENTER

key.

31. Press the

down ▼ arrow key until CAL

Voltage 45%

is displayed.

32. Press the CHANGE key. CAL Voltage 45%

will begin to flash.

33. The oxygen level at the 45% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

45% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

5.2 %

<100 ppm

<100 ppm

34. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.

35. Once the oxygen level is within the specified

range at 45%, press the ENTER key to store
the selected blower output voltage for the
45% valve position.

36. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

37. Press the CHANGE key. SET Valve Position

will begin to flash.

38. Press the ▼ arrow key until the SET Valve

Position

reads 30%, then press the ENTER

key.

39. Press the

▼ arrow key until CAL Voltage

30%

is displayed.

40. Press the CHANGE key. CAL Voltage 30%

will begin to flash.

41. The oxygen level at the 30% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

30% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

6.0 %

<100 ppm

<100 ppm


42. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.


43. Once the oxygen level is within the specified

range at 30%, press the ENTER key to store
the selected blower output voltage for the
30% valve position.

44. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

45. Press the CHANGE key. SET Valve Position

will begin to flash.

46. Press the ▼ arrow key until the SET Valve

Position

reads 18%, then press the ENTER

key.

4-8