TROUBLESHOOTING

TABLE 8-1. BOILER TROUBLESHOOTING

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

AIRFLOW FAULT

DURING IGNITION

1. Blower stopped running due to thermal or

current overload

2. Blocked Blower inlet or inlet ductwork

3. Blocked Blower proof switch

4. Blocked blocked-air inlet switch

5. Defective Blower proof switch



6. Defective blocked-air inlet switch



7. Loose temperature to AUX connection in

I/O Box

8. Defective temperature sensor

9. Loose wire connection between the 0-

10V signal from I/O box to the Blower
Motor input

10. Defective I/O box

11. Wrong 0-10V output selection on the

control box

12. Defective Air-Fuel Valve potentiometer


13. Fuel Selector Switch set to incorrect

position for fuel used.

1. Check combustion blower for signs of excessive heat or high

current drain that may trip thermal or current overload devices.

2. Inspect the inlet to the combustion blower including any ductwork

leading up to the combustion blower for signs of blockage.

3. Remove the Blower proof switch and inspect for signs of

blockage, clean or replace as necessary.

4. Remove the blocked-air inlet switch and inspect for signs of

blockage, clean or replace as necessary.

5. Measure the Blower proof switch for continuity with the

combustion blower running. If there is an erratic resistance
reading or the resistance reading is greater than zero ohms,
replace the switch.

6. Measure the blocked-air inlet switch for continuity with the

combustion blower running. If there is an erratic resistance
reading or the resistance reading is greater than zero ohms,
replace the switch.

7. Check the actual inlet air temperature and measure voltage at

AUX input in the I/O Box. Verify that the voltage conforms to the
values shown in the tabular listing provided in Appendix C.

8. Refer to CORRECTIVE ACTION 7 and verify that the voltage

conforms to the values shown in Appendix C.

9. Check wire connection from I/O Box 0-10V signal to the Blower

Motor.

10. Measure voltage at the I/O box 0-10V output. A voltage of 8.2V

equates to a 100% valve position.

11. Check the Analog Out option on the C-More Configuration Menu.

Valve Position 0-10V should be selected.

12. Check Air/Fuel Valve position at 0%, 50% and 100%. the

position on the C-More VALVE POSITION bargraph should
match the valve position dial on the Air/Fuel Valve.

13. Check position of Fuel Selector Switch

8-2