E8 Controller and BCM for Modulex EXT

Installation, Operation & Maintenance Manual

CHAPTER 3: E8 CONTROLLER OPERATION

OMM-0093_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page

13 of 108

GF-136-C

Ph.: 800-526-0288

PRI: 06/24/2013

3.1.3 MENU Mode Operation (Door Open)

Opening the E8 controller hinged door reveals the E8 controls (below) and initiates MENU

Mode, which enables access to an extensive set of software menus.

E8 FRONT PANEL: Controls and Indicators

Figure 3-3: E8 Display Controls and Indicators

ITEM

FUNCTION

A

LCD display: Selected Menu/Sub-menus, parameter names/values, and selected

busses are indicated in the LCD display when in MENU Mode.

B

Mounting Key Access Holes: Insert narrow screwdriver deep into holes and lift up

controller to remove.

C

Change LED: When lit, this LED indicates that the value shown in the display can be

changed using the Rotary Knob (

G).

D

Optical Adaptor: For PC connection

E

Program Key: Used to select a sub-menu level, select a parameter value to change, or

save a new parameter value.

F

Manual/Automatic Switch: A 2-position (10/2 o’clock) screwdriver adjustable switch.

Normally, this switch is set to the Automatic (2 o’clock) position to allow program control

of the boiler.

When set to the Manual (10 o’clock) position, a flashing “EMERG –

MODE” message is displayed. Heating Circuit 1 (HC1) pump and the first burner stage

are switched on. Pumps for Heating Circuit 2 (HC2) and Domestic Hot Water (DHW)

will also be switched on if sensors are installed and enabled. The pump(s) will turn off

when the flow temperature reaches the value set for MAX T-FLOW (in EXPERT/HEAT

CIRCUIT 1 menu). The first burner stage will cut off when the boiler temperature

reaches the value set for MAX T-MODUL (in EXPERT/INSTALLATION menu).

G

Rotary Knob: Used to navigate through menus and parameters or adjust

parameters.