6.3.2 Configuring Remote Signal Source

Configure the Remote Signal Source as shown in the instructions below.

Configuring Remote Signal Source

1. Ensure ON/OFF switch on front of Modulex boiler is in the ON position.

2. Open Controller front panel.

3. Turn Rotary Knob clockwise to

EXPERT menu. The first sub-menu displayed will be

INSTALLATION (sub-menu items scroll in this sequence: INSTALLATION, HOT

WATER, HEAT CIRCUIT 1, HEAT CIRCUIT 2, SOLAR / MF). Continue scrolling

(clockwise) through the

EXPERT menu until SOLAR / MF is displayed.

4. With

SOLAR / MF displayed, press the Program Key to enter the SOLAR / MF sub-menu.

5. Scroll through the

SOLAR / MF sub-menu by turning Rotary Knob clockwise until the F-15

FUNCTION is displayed along with it’s presently stored value (default is 00).

6. Press Program Key to change the F-15

FUNCTION. Display will show CODE NO.,

requesting valid code to be entered.

7. Enter code

0000 (four zeros) by pressing the Program Key four times. The red LED will

remain lit while the four code digits are entered.

8. With

F-15 FUNCTION displayed again and red LED lit, turn Rotary Knob to change the F-

15 FUNCTION to 01.

9. Press the Program Key to store the 01 setting for the

F-15 FUNCTION. The red LED will

go off.

10. Continue scrolling through the sub-menu until

RETURN is displayed.

11. Press the Program Key to exit the

SOLAR / MF sub-menu.

12. With SOLAR / MF displayed, turn Rotary Knob counter-clockwise until the

INSTALLATION sub-menu is displayed in the LCD.

13. With

INSTALLATION displayed in the LCD, proceed directly to Section 6.3.3.

NOTE

When navigating the menus during configuration and you scroll

past the SOLAR / MF item, the EXPERT HS menu will be

displayed. If this occurs, slowly turn the Rotary Knob

counterclockwise until SOLAR / MF is again displayed.