CHAPTER 6: E8 SETUP AND PROGRAMMING

The following sections provide the detailed set-up and programming procedures necessary to

configure the Modulex Boiler for service operation.

NOTE

When performing the following operating mode set-up procedures,

refer to Chapter 3 of this document for illustrations and

descriptions of the Controller operating controls and displays.

Refer to Chapter 6 for Controller wiring connections.

6.1 Indoor/Outdoor Reset Mode

This mode is used to adjust the boiler set point based on the outdoor air temperature and a

programmed heating curve. The heating curve can be customized using functions provided in

the USER menu. The outdoor air sensor provided with the Modulex boiler must be installed to

enable this mode of operation. The following sections provide the procedures necessary to

wire and configure the controller for operation in the Indoor/Outdoor Reset mode.

6.1.1 Wiring Connections

The outdoor air sensor provided with the boiler should be mounted on the outer North or

North-East side of the building away from windows, doors and vents. Never mount the outdoor

air sensor in a location where it is exposed to direct sunlight.
Wire the sensor using shielded 2-conductor, 18 AWG wire (Belden #8760, or equiv.). Connect

the outdoor air sensor wire leads to terminals 9 (F9) and 10 (GND) of Connector 1 on the rear

of the Controller. There is no polarity to observe when connecting the wire leads. Refer to the

wiring diagrams in Chapter 7 for the locations of sensor connections. This sensor must be

connected (Section 7.1.2) prior to configuring the Controller.

6.1.2 Indoor/Outdoor Reset Operation Configuration

The Indoor/Outdoor Reset Mode is configured using the USER menu as shown in instructions

on the next page.

IMPORTANT

The outdoor air sensor MUST be connected as described in

Section 5.1.1 above, prior to configuring the Controller for

Indoor/Outdoor Reset Mode operation.