1 operating scenario, E8 controller and bcm for modulex ext – AERCO Modulex E8 Controller (and BCM) For Modulex EXT Boilers User Manual

Page 82

Advertising
background image

E8 Controller and BCM for Modulex EXT

Installation, Operation & Maintenance Manual

CHAPTER 8: BOILER COMMUNICATION MODULE (BCM)

Page

82 of 108

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0093_0A

PRI: 06/24/2013

Phone: 800-526-0288

GF-136-C

Figure 8-5: Installing Resistor to Change Default Setpoint

8.4 BCM Configured as Primary Controller Utilizing Modbus

The BCM can be configured as the Primary Controller, instead of the E8, when it is connected

to a Modbus Network. However, the E8 must be disconnected from the e-Bus connection on

the BCM Board (see Section 8.4.3). All Modbus Networks are implemented utilizing a “Master –

Slave” scenario where only one device, the “Master”, can initiate a communication sequence.

However, BCMs can only function as “Slave” devices on a Modbus Network. Therefore, the

BCM must be interfaced to an external controlling “Master”. The “Master” can be AERCO’s

Boiler Management System II (BMS II), AERCO Control System (ACS), or an Energy

Management System (EMS)/Building Automation System (BAS) developed by other

manufacturers.
The following subordinate sections provide descriptions of Modbus Network operation and

required wiring connections between the BCM “Slaves and the controlling “Master” (EMS, BAS).
Detailed information on the Modbus Function Codes, Input/Holding Register Assignments and

other Modbus requirements supported by the BCM are provided in Chapter 9 of this document.

8.4.1 Operating Scenario

An EMS or BAS Master can control the Networked Modulex Boilers utilizing Remote Setpoint.

An AERCO BMS II Master can control the networked Modulex boilers utilizing a Modbus signal.
In the event that the external control signal from the Master BMS II or ACS, EMS, or BAS is lost,

the BCM will assume control of the Modulex Boilers, if enabled. When this occurs, the BCM will

maintain the boiler at a constant setpoint based on the resistor installed between terminals 6