BG1600M Intermittent Pilot Ignition Control Installation Instructions 11

No

Yes

Continued

from previous page

Pilot is lit

Main burner

failed to turn

on?

24V between

MV and MV/PV

terminals?

Yes

No

Yes

No

Check that shutoff valves are on.

Check wiring to main valve.

Check tubing is clear.

If all OK replace main valve.

Yes

No

Replace

module.

Yes

Yes

No

Gas at main

burner?

Adjust pilot flame size

and position, or replace

pilot burner or main burner.

After main is

lit, do valves turn off

and start new

cycle?

Pilot flame in

contact with spark or

sense electrode?

Adjust pilot flame size or

electrode position.

Replace

module.

No

Two rod

flame sense?

Yes

Check wiring electrode

to SENSE terminal.

If OK replace module.

Control is

operating

normally.

Figure 9: Troubleshooting Flow Chart (2 of 2)