BG1600M Intermittent Pilot Ignition Control Installation Instructions 3

MV

MV/PV
(COM)

PV

GN

D

B

URNE

R

GND

24V

TH

SENSE

INT

E

RNA

L

SPARK

Thermostat

High

Temp

Limit

Pilot

Burner/ignitor

Combination

Gas Valve

24VAC
Class 2
Transformer

1

2

3

4

5

6

7

8

10

9

L1 (Hot)

L2 (Neu)

1

2

3

4

1

2

Power Supply. Provides disconnect means and overload protection as required.

Maximum cable length 48 inches (1,220 mm). (Resistive wire recommended.)

4

3

Alternate location for limit controller.

Controls in 24V circuit must not be in ground leg to transformer.

Chassis or Frame

Ground

5

Sensor rod must be 3/8” (9.53 mm) to 1/2” (12.7 mm) of the sensor tip should
be in the flame for proper sensing signal.

5

Figure 1: Wiring for 1 Rod Flame Sense without Vent Damper Jumper Plug

MV

MV/PV
(COM)

PV

GN

D

B

URNE

R

GND

24V

TH

SENSE

INT

E

RNA

L

SPARK

Thermostat

High

Temp

Limit

Pilot

Burner/ignitor

Combination

Gas Valve

24VAC
Class 2
Transformer

1

2

3

4

5

6

7

8

10

9

L1 (Hot)

L2 (Neu)

1

2

3

4

1

2

Power Supply. Provides disconnect means and overload protection as required.

Maximum cable length 48 inches (1,220 mm). (Resistive wire recommended.)

4

3

Alternate location for limit controller.

Controls in 24V circuit must not be in ground leg to transformer.

Chassis or Frame

Ground

5

Sensor rod must be 3/8” (9.53 mm) to 1/2” (12.7 mm) of the sensor tip should
be in the flame for proper sensing signal.

Use jumper
plug supplied
with control.

5

Figure 2: Wiring for 1 Rod Flame Sense with Vent Damper Jumper Plug