BASO BG1600M 2014 User Manual

Page 9

Advertising
background image

BG1600M Intermittent Pilot Ignition Control Installation Instructions 9

No

Yes

Idle State

Call for heat

from the thermostat

If damper connected

wait for it to open

POWER TO CONTROL

One second for

diagnostic routines

If pre-purge wait

flashing red LED once a

0.5 second until over

Turn on spark and

pilot gas valve
start trial timer

Spark on 4 seconds

blinking red LED rapidly

spark off 1 second

Flame

on?

Flame

on?

Wait 0.5 second

Trial

over?

No

Turn on main

gas valve and red LED

reset try count

Yes

No

Turn pilot gas

valve off

Yes

Retry

option?

Wait 5 or 60 minutes,

blink red LED every 4 seconds

TRIAL

TIME

LOOP

TRIAL

TIME

OVER

RESTART

Note: If the thermostat opens,
the control will turn off valves
and returns to the idle state.

Wait 0.1 second

checking memory and

relay driver circuits

OK

Flame

on?

Yes

No

Flame off

0.7 second?

Turn pilot and main

gas valves off

wait 0.7 second

inter-purge blinking

red LED once a 0.5 second

Yes

No

FLAME LOST

FLAME ON

LOOP

RELIGHT

Note:

Error Codes

Lock out on timeout or fault detected,

turn off relays and spark loop blinking
error code until power off.

No flame in trial time.
Flame sense stuck on.
Pilot relay driver fault.
Main relay driver fault.
Processor errors.

1 Blink
2 Blinks
3 Blinks
4 Blinks
5 to 9 Blinks

Yes

Lockout

Re-Ignition

RECYCLE

No

Yes

Turn main gas

valve off, start spark

and trial timer

RE-IGNITION

Tries over

Figure 7: Sequence of Operation

Advertising