background image

BG1600M Intermittent Pilot Ignition Control Installation Instructions 15

Technical Specification

Product

BG1600M Intermittent Pilot Ignition Control

Ignition Type

Indirect

Ignition Source

High voltage spark, capacitive discharge

High Voltage Cable
Maximum Length

48 in. (1,220 mm) (Resistive wire recommended, rated for at least 15kV.)

Flame Sense Cable
Maximum Length

48 in. (1,220 mm)

Flame Detection Means

Flame Rectification

Flame Detection Type

Local or Remote

Minimum Flame Current

0.15 microamperes

Flame Failure Response
Time

2 seconds maximum

Maximum Spark Gap

0.2 in. (5.1 mm)

Number of Trials Before
100% Shutoff

One or Three

Trial-for-Ignition Time

Infinite, 8, 15, 25, 50, 85, 90 or 120 seconds

Prepurge Time

0 (none), 4, 10, 15 or 30 seconds

Inter-Purge Time

0 (none), 5, 15 or 30 seconds

Retry (Recycle) Delay
Period

0 minutes (none)
5 minutes
60 minutes

Power Requirements

Control:
Operation Current:

24 VAC (+/- 20%), 50/60 Hz
0.2 A nominal + valves

Contact Rating

Main Valve:
Pilot Valve:

2 A maximum
1 A maximum

Wiring Connections

1/4 in. (6.35 mm) male spade

Maximum Firing Rate

400,000 Btu/hr (117 kW)

Ambient Operating and
Storage Temperature

-40 to 170

°F (-40 to 77°C)

Humidity

95% RH noncondensing

Type of Gas

Natural, Liquefied Petroleum (LP), Manufactured, Mixed or LP Gas-Air Mixture

Packaging

Bulk pack supplied to original equipment manufacturer (25 per box)
Individual pack (1 per box)
Individual overpack (20 per box)

Pack Weight

Bulk pack 14 lb (6.36 kg)
Individual pack 1 lb (.454 kg)
Individual overpack 18 lb (8.17 kg)

Agency Listing

CSA Certificate Number 246569-2161442

Specifications Standards

ANSI Standard Z21.20
CAN/CSA-C22.2 No. 199

The performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is
performed under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and
may void the warranty. If the product is exposed to water (dripping, spraying, rain, etc.) or other harsh environments, it must be protected. The
original equipment manufacturer or end user is responsible for the correct application of BASO products. For questionable applications, please
consult BASO Gas Products LLC. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from
misapplication or misuse of its products.

1007 South 12th Street
PO Box 170
Watertown, WI 53094

Published in U.S.A.