Caution, Property damage hazard – Kenmore POWER MISER 153.330652 User Manual

Page 13

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

This water heater shall not be connected to any heating
systems or component(s) used with a non-potable water heating

appliance.

All piping components connected to this unit for space heating

applications shall be suitable for use with potable water.

Toxic chemicals, such as those used for boiler treatment shall

not be introduced into this system.

Water supply systems may, because of such events as high line

pressure, frequent cut-offs or the effects of water hammer, have
installed devices such as pressure reducing valves, check valves,
back flow preventers, etc. to control these types of problems.

When these devices are not equipped with an internal by-pass,

and no other measures are taken, the devices cause the water

system to be closed. As water is heated, it expands (thermal
expansion) and closed systems do not allow for the expansion
of heated water.

The water within the water heater tank expands as it is heated

and increases the pressure of the water system. If the relieving
point of the water heater’s temperature-pressure relief valve
is reached, the valve will relieve the excess pressure. The

temperature-pressure relief valve is not intended for the

constant relief of thermal expansion. This is an unacceptable
condition and must be corrected. It is recommended that any

devices installed which could create a closed system have a

by-pass and/or the system have an expansion tank to relieve the
pressure built by thermal expansion in the water system. Refer

to the Thermal Expansion section under Troubleshooting Guide
or contact local plumbing authority or local Sears Service Center
on how to control this situation.

NOTE: To protect against untimely corrosion of hot and cold

water fittings, it is strongly recommended that di-electric

unions or couplings be installed on this water heater when
connected to copper pipe.

CAUTION

* •

Property Damage Hazard

' Avoid water heater damage.

' Install thermal expansion tank if necessary.

' Do not apply heat to cold water inlet.

' Contact qualified installer or Sears Service Center.

Look at the top of the water heater. The cold water inlet is
marked “COLD”. Put two or three turns of Teflon tape around

the threaded end of the threaded-to-sweat coupling and
around both ends of the 3/4” NPT threaded nipple. Using

flexible connectors, connect the cold water pipe to the cold
water inlet of the water heater.

NOTE: This water heater is super insulated to minimize
heat loss from the tank. Further reduction in heat loss

can be accomplished by insulating the hot water lines
from the water heater.

INSTALLATION COMPLETED USING

INSTALLATION KIT

FLEXIBLE

WATER

CONNECTORS

HOT WATER

OUTLET

THREADED TO

SWEAT COUPLING

3/4” THREADED -

COUPLING T

DRAFT HOOD,

SHUTOFF

VALVE

1

1C ^

I

THREADED TO

SWEAT COUPÜNG

-3/4" THREADED
\ COUPLING

- TEMPERATURE-

PRESSURE

RELIEF VALVE

COLD WATER

INLET

''DISCHARGE PIPE

(Do not cap or plug)

Vti r

6” MAXIMUM

AIR GAP

- FLOOR DRAIN

FIGURE 15.

T & P Valve and Pipe Insulation

Remove insulation for T & P valve and pipe connections from

carton.

Figure 15 shows the typical attachment of the water piping to

the water heater. The water heater is equipped with 3/4” NPT

water connections.

NOTE: If using copper tubing, solder tubing to an adapter
before attaching the adapter to the cold water inlet
connection. Do not solder the cold water supply line directly

to the cold water inlet. It will harm the dip tube and damage
the tank.

• Look at the top cover of the water heater. The water outlet is

marked “HOT”. Put two or three turns of Teflon tape around the

threaded end of the threaded-to-sweat coupling and around

both ends of the 3/4” NPT threaded nipple. Using flexible
connectors, connect the hot water pipe to the hot water outlet

on the water heater.

(R)

TEFLON is a registered trademark of E.l. Du Pont De Nemours and Company.

PIPE

INSULATION

FLUE PIPE

FIGURE 15A.

Fit pipe insulation over the incoming cold water line and the hot

water line. Make sure that the insulation is against the top cover

of the heater.

13

Advertising
This manual is related to the following products: