Temperature-pressure relief valve, Temperature pressure relief valve -14, Caution – Kenmore POWER MISER 153.330652 User Manual

Page 14: Warning, Adanger

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

FitT & P valve insulation over valve. Make sure that the insulation

does not interfere with the lever of the T & P valve.

Secure all insulation using tape.

Temperature-Pressure Relief Valve

A

warning

Explosion Hazard

Temperature-pressure relief valve

must comply with ANSI Z21.22
and ASME code.

Properly sized temperature-
pressure relief valve must be
installed in opening provided.

Can result in overheating
excessive tank pressure.

and

Can cause serious injury or death.

This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed
equipment as meeting the requirements for Relief Valves for Hot
Water Supply Systems, ANSI Z21.22 and the code requirements
ofASME.

If replaced, the valve must meet the requirements of local codes,

but not less than a combination temperature and pressure relief

valve certified as indicated in the above paragraph.

The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water

heater (150 psi = 1,035kPa) and a discharge capacity not less

than the water heater input rate as shown on the model rating

plate.

For safe operation of the water heater, the relief valve must not
be removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly

into the fitting of the water heater designed for the relief valve.
Position the valve downward and provide tubing so that any

discharge will exit only within 6 inches (153 mm) above, or

at any distance below the structural floor, see Figure 16. Be
certain that no contact is made with any live electrical part.

The discharge opening must not be blocked or reduced in
size under any circumstances. Excessive length, over 30 feet

(9.14 m), or use of more than four elbows can cause restriction
and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief

valve and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided. To prevent bodily

injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances

demand. If the discharge pipe is not connected to a drain or other
suitable means, the water flow may cause property damage.

CAUTION

Water Damage Hazard

■ Temperature-pressure relief valve discharge

pipe must terminate at adequate drain.

The Discharge Pipe:

• Shall not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

• Shall not be plugged or blocked.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both the

temperature-pressure relief valve, and the discharge pipe.

• Shall terminate a maximum of six inches above a floor drain

or external to the building. In cold climates, it is recommended
that the discharge pipe be terminated at an adequate drain

inside the building.

• Shall terminate at an adequate drain.
• Shall not have any valve between the relief valve and tank.

ADANGER

Water temperature over 125°F

(52°C) can cause severe burns
instantly resulting in severe injury
or death.

Children, the elderly, and the
physically or mentally disabled
are at highest riskforscald injury.

Feel water before bathing or

showering.

Temperature limiting valves are

available.

Read instruction manual for safe

temperature setting.

14

Advertising
This manual is related to the following products: