Gr-1089 installation and caution instructions – Cisco 5000 Series User Manual

Page 120

Advertising
background image

S e n d d o c u m e n t a t i o n c o m m e n t s t o n e x u s 5 k d o c s @ c i s c o . c o m

B-8

Cisco Nexus 5000 Series Hardware Installation Guide

OL-15902-01

Appendix B Technical Specifications

GR-1089 Installation and Caution Instructions

GR-1089 Installation and Caution Instructions

The following are NEBS GR-1089 installation and caution instructions:

Shielded cable, grounded at both ends, is specified for copper telecom ports.

Caution

The intra-building port(s) of the equipment or subassembly is suitable for connection to
intra-building or unexposed wiring or cabling only. The intra-building port(s) of the
equipment or subassembly must not be metallically connected to interfaces that connect to the
OSP or its wiring. These interfaces are designed for use as intra-building interfaces only (Type
2 or Type 4 ports as described in GR-1089-CORE, Issue 4) and require isolation from the
exposed OSP cabling. The addition of primary protectors is not sufficient protection in order
to connect these interfaces metallically to OSP wiring.

The Cisco Nexus 5500 Platform switches and the Cisco Nexus 5000 Series switches have AC power
ports that are intended for deployments where an external Surge Protective Device (SPD) is utilized
at the AC power service equipment (see definition in National Electric Code).

The Cisco Nexus 5500 Platform switches and the Cisco Nexus 5000 Series switches are designed
for a Common Bonding Network (CBN) installation.

The Cisco Nexus 5500 Platform switches and the Cisco Nexus 5000 Series switches can be installed
in

network telecommunication facilities or

locations where the National Electric Code applies.

An electrical conducting path shall exist between the product chassis and the metal surface of the
enclosure or rack in which it is mounted or to a grounding conductor. Electrical continuity shall be
provided by using thread-forming type mounting screws that remove any paint or nonconductive
coatings and establish a metal-to-metal contact. Any paint or other nonconductive coatings shall be
removed on the surfaces between the mounting hardware and the enclosure or rack. The surfaces
shall be cleaned and an antioxidant applied before installation.

The DC return connection to this system should remain isolated from the system frame and chassis
(DC-I).

The nominal DC operating voltage –48 VDC.

ATT NEBS Requirements

ATT TP76200 level 3 TCG Checklist

ETSI

ETS 300 019-2-1, Class 1.2 Storage

ETS 300 019-2-2, Class 2.3 Transportation

ETS 300 019-2-3, Class 3.2 Stationary Use

Table 16

NEBS Compliance and ETSI 300-019 Environmental Requirements

Specification

Description

Advertising