Chapter 5. Programming the PLC
DeviceMaster UP EtherNet/IP User Guide: 2000424 Rev. L
Send Consumed Sequence Number to DeviceMaster UP
5.3.7.4. Send Consumed Sequence Number to DeviceMaster UP
Use the Configuration tab on the Message Configuration dialog to update the consumed sequence number for a
specified port on the DeviceMaster UP. Only the Write-to-Tag-Synced receive method uses this feature.
Provide the following information:
Field
Selection
Message Type
CIP Generic
Service Type
Set Attribute Single
Service Code
10 Hex (Set Attribute Single)
Class
71 Hex (Serial Port Data Transfer object)
Instance
1 (Port 1)
Attribute
4 (Receive consumed sequence number attribute)
Source Element Com1_ConRxSeq (one INT)
Source Length
2 (one INT)