146 -

Chapter 5. Programming the PLC

DeviceMaster UP EtherNet/IP User Guide: 2000424 Rev. L

Configure the DeviceMaster UP for the RSLogix 5 Program

6.

Set the serial port settings under EtherNet/IP Settings to the following values.

7.

Click Submit.

Field

Settings

TX Sequence Number
Checking.

Select

Rx (To PLC) Ethernet
Transfer Method

•

Set to Polling for lpbkExampleSlcMsgPollRS5 and
lpbkExamplePlc5MsgPollRS5.

•

Set to Write-to-Tag/File for lpbkExamplePlc5MsgFileRS5.

•

Set to Write-to-Tag/File-Synced for lpbkExamplePlc5MsgFileSyncRS5.

PLC IP Address

•

Leave blank for Polling.

•

Set to IP Address of PLC for Write-to-Tag/File and Write-to-Tag/File-
Synced.

PLC Controller Slot Number Unused and can remain blank.

Rx (To PLC) Produced Data
Tag/File Name

•

Leave blank for Polling.

•

Set to $N10:0, the PLC receive filename for Write-to-File and Write-to-
File-Synced.

Reset Port

Select

Save in Flash

Select