Chapter 5. Programming the PLC
DeviceMaster UP EtherNet/IP User Guide: 2000424 Rev. L
Configure the DeviceMaster UP for the RSLogix 5 Program
6.
Set the serial port settings under EtherNet/IP Settings to the following values.
7.
Click Submit.
Field
Settings
TX Sequence Number
Checking.
Select
Rx (To PLC) Ethernet
Transfer Method
•
Set to Polling for lpbkExampleSlcMsgPollRS5 and
lpbkExamplePlc5MsgPollRS5.
•
Set to Write-to-Tag/File for lpbkExamplePlc5MsgFileRS5.
•
Set to Write-to-Tag/File-Synced for lpbkExamplePlc5MsgFileSyncRS5.
PLC IP Address
•
Leave blank for Polling.
•
Set to IP Address of PLC for Write-to-Tag/File and Write-to-Tag/File-
Synced.
PLC Controller Slot Number Unused and can remain blank.
Rx (To PLC) Produced Data
Tag/File Name
•
Leave blank for Polling.
•
Set to $N10:0, the PLC receive filename for Write-to-File and Write-to-
File-Synced.
Reset Port
Select
Save in Flash
Select