DeviceMaster UP EtherNet/IP User Guide: 2000424 Rev. L

Chapter 5. Programming the PLC - 115

Modifying an RSLogix 5000 PLC Program Example (Older Versions)

-

5.3.5. loopbackExamplePolling.L5K

on Page 106

•

If you still have problems loading the example .L5K file, go to the next step.

7.

Make the following modifications to the .L5K file:

•

Modify the ProcessorType setting in the example .L5K file to match the ProcessorType in the known
functional .L5K file (line 10 of the example .L5K file).

•

Replace the MODULE local section of the example .L5K file with the Module local section in the known
functional .L5K file (lines 89 to 102).

•

Choose one of the following options:

-

Replace the MODULE EnetBridge section of the example .L5K file with the EtherNet/IP interface
section from the known functional .L5K file.

-

Delete the MODULE EnetBridge section from the example file (lines 104 to 117).

8.

Load the example .L5K file into RSLogix 5000.

•

If it loads without errors, follow the appropriate process to modify the example program to run on your
system. The following topics describes how to modify the example.L5K files:

-

5.3.3. loopbackExampleTagWrite.L5K

on Page 104

-

5.3.4. loopbackExampleTagWriteSynced.L5K

on Page 105

-

5.3.5. loopbackExamplePolling.L5K

on Page 106

•

If you still have problems loading the example.L5K file, remove or modify all references to EnetBridge
in the example .L5K file and re-load the example .L5K file into RSLogix 5000.