Table 2 — Electrical Data (cont)

LEGEND

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,

380 v, 480 v, and 575 v. Heaters are rated at 240 v, 380 v, 480 v, or
600 v. If power distribution voltage to unit varies from rated heater
voltage, heater kW will vary accordingly.

†Fuse or HACR circuit breaker.

**Heaters are field installed only.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance.

% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

3. MCA calculation for units with electric heaters over 50 kW =

(1.25 x IFM amps) + (1.00 x heater FLA).

UNIT
50TJ

NOMINAL

VOLTAGE

(3 Ph,

60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

ELECTRIC

HEAT*

POWER

SUPPLY

No. 1

No. 2

Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp

FLA

FLA LRA

kW

FLA

MCA

MOCP†

028

(25 Tons)

208/230

187

253

41.0 350 37.8 239

2

1

6.6

10.0 28.0/28.0

130/130 150/150

4.6

18.8

135/135 175/175

26/34

71/82

130/138 150/150

4.6

18.8

26/34

71/82

135/143 175/175

42/56

117/135 181/170 200/175

4.6

18.8

42/56

117/135 187/176 200/200

-

56/75** 156/180 191/215 200/225

4.6

18.8 56/75** 156/180 197/221 200/225

380

342

418

21.8 151 21.2 145

2

1

3.9

10.0

17.0

73

90

2.3

6.0

76

90

20

30

73

90

2.3

6.0

20

30

76

90

35

52

87

90

2.3

6.0

35

52

90

90

460

414

508

21.8 158 17.2 125

2

1

2.8

10.0

14.6

66

80

2.3

6.0

68

80

32

39

67

80

2.3

6.0

32

39

70

80

55

66

84

90

2.3

6.0

55

66

87

100

80**

96

114

125

2.3

6.0

80**

96

117

125

575

518

633

17.3 125 12.4

80

2

1

3.4

10.0

13.0

54

70

2.1

4.8

56

70

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.