Belt tension adjustment, Condenser-fan adjustment – Carrier 50TJ016-028 User Manual

Page 26

Advertising
background image

26

Belt Tension Adjustment —

To adjust belt tension:

1. Loosen fan motor bolts.
2. Adjust belt tension:

a. Size 016 Units: Move motor mounting plate up or

down for proper belt tension (

1

/

2

in. deflection with

one finger).

b. Size 020-028 Units: Turn motor jacking bolt to move

motor mounting plate up or down for proper belt ten-
sion (

3

/

8

in. deflection at midspan with one finger [9

lb force]).

3. Tighten nuts.
4. Adjust bolts and nut on mounting plate to secure motor in

fixed position.

Condenser-Fan Adjustment

50TJ016,020 UNITS (Fig. 34)

1. Shut off unit power supply.
2. Remove access panel(s) closest to the fan to be adjusted.
3. Loosen fan hub setscrews.
4. Adjust fan height on shaft using a straightedge placed

across the fan orifice.

5. Tighten setscrews and replace panel(s).
6. Turn on unit power.

50TJ024,028 UNITS (Fig. 35)

1. Shut off unit power supply.
2. Remove fan top-grille assembly and loosen fan hub

screws.

3. Adjust fan height on unit, using a straightedge placed

across the fan orifice.

4. Tighten setscrews and replace rubber hubcap to prevent

hub from rusting to motor shaft.

5. Fill hub recess with permagum if rubber hubcap is

missing.

Fig. 32 — 50TJ016 Evaporator-Fan

Motor Section

NOTE: A 3

1

/

2

-in. bolt and threaded plate are included in the

installer’s packet. They should be added to the motor support chan-
nel below the motor mounting plate to aid in raising the motor. The
plate part number is 50DP503842. The adjustment bolt is

3

/

8

-16 x

1

3

/

4

in.-LG.

Fig. 33 — 50TJ020-028 Evaporator-Fan

Motor Section

NOTE: Dimensions are in inches.

Fig. 35 — Condenser-Fan Adjustment,

50TJ024,028

NOTE: Dimensions are in inches).

Fig. 34 — Condenser-Fan Adjustment,

50TJ016,020