Carrier 50TJ016-028 User Manual

Page 13

Advertising
background image

13

COMMISSIONING — The EconoMi$er saves energy when
it uses outdoor air to provide free cooling instead of mechani-
cal air conditioning. The EconoMi$er switchover strategy de-
termines if the outdoor air is suitable for free cooling. The
EconoMi$er chooses the switchover strategy with the most en-
ergy savings, provided that the required sensors are connected
and functioning normally.

Refer to Table 4 to determine the sensors required for each

strategy.
Differential Enthalpy Switchover Strategy — The differen-
tial enthalpy switchover strategy must be selected manually, if
required. To enable, press and hold the CONFIG button for 30
seconds, then release. The LED will flash twice to indicate the
change of configuration.

To return to single enthalpy mode, press and hold the CON-

FIG button for 30 seconds. The LED will flash once to indicate
the change of configuration.
DISCHARGE AIR THERMISTOR (DAT) — The discharge
air thermistor is factory-mounted on the supply-fan housing in
the fan section of the unit. The DAT is factory-wired to the
EconoMi$er Control Module.
CO

2

CONTROL SETUP — If a CO

2

sensor is not being

used, proceed to the next section. If a CO

2

sensor is being used,

perform the following:

1. Determine the value at which you want the minimum

position of the dampers to begin opening to allow a
greater amount of outdoor air to enter. The range is
800 to 1,400 ppm.

2. Locate the CO

2

SP (PPM) potentiometer and adjust to the

desired set point. See Fig. 16.

IMPORTANT: If a sensor stops functioning nor-
mally (becomes unreliable), the EconoMi$er
switches to the next best strategy.

SENSOR
COVER

OUTSIDE AIR SENSOR

MOUNTING
SCREW

MOUNTING SCREW

WIRING
HARNESS

SENSOR
WIRING
CONNECTIONS

Fig. 22 — Outdoor-Air Sensor Details

Fig. 21 — Outdoor-Air Sensor Location

Fig. 19 — Seal Strip Location

(Air Hood Cross-Sectional View)

NOTE: The outdoor-air hood comes with a baffle which is used on
028 units only; discard baffle for 016-024 units.

Fig. 20 — Outdoor-Air Hood Details

HOOD TOP
PANEL

HOOD SIDE
PANELS (2)

BAFFLE
(028 ONLY)

LOWER
FILTER
RETAINER

FILTER SUPPORT
BRACKET

HOOD DRAIN PAN

UPPER FILTER RETAINER

BAFFLE (028 ONLY)

LOWER FILTER
RETAINER

FILTER SUPPORT
BRACKET

Advertising