EVCO S.p.A.
EVF818 | Installer manual ver. 1.0 | Code 144F818E104
page 15 of 76
4
ELECTRIC CONNECTION
4.1
Electric connection
The following drawing illustrates the EVF818 electric connection.
The utility managed by the K7 output, depends on parameter u11, as follows:
-
cabinet light (u11 = 0, pre-defined setting)
-
UV light (u11 = 1).
For the settings relative to the parameters, see chapter 10 “CONFIGURATION”.
The utility managed by the K8 output, depends on parameter u1, as follows:
-
pump down valve (u1 = 0, per-defined setting)
-
alarm (u1 = 1).
For the settings relative to the parameters, see chapter 10 “CONFIGURATION”.
The TTL port is the port used for connection of the controller to the EVKEY programming key.