FloAire INDIRECT FIRED BENT TUBE MODULE User Manual

Page 20

Advertising
background image

20

Maximum RPM and HP Chart

Blower Size Maximum RPM

Maximum HP

10”

1800

2

12”

1500

3

15”

1400

5

18”

1200

5

20”

1000

10

25”

900

20

Pulley Adjustment Illustration

Final Start-Up Procedure

1. With the air and burner systems in full operation and all ducts attached, measure the system

airflow. Motor sheave (pulley) is variable pitch, and allows for an increase or decrease of the fan
RPM to adjust the airflow, as shown in the illustration below. For your convenience, a RPM chart
is included in the following pages.

2. Once the proper airflow is achieved, measure and record the fan speed with a reliable

tachometer. Caution - Excessive speed will result in motor overloading or bearing failure.
Do not set fan RPMs higher than specified in the maximum RPM chart. See the
troubleshooting guide for more information.

3. Measure and record the voltage and amperage to the motor and compare with the motor

nameplate to determine if the motor is operating under safe load condition.

4. Once the rpm of the ventilator has been properly set, disconnect power and recheck belt tension

and pulley alignment as described below.

Advertising
This manual is related to the following products: