Optional Mixing Box Filters

Diagonal Filters

Unit Size

Filter Quantity

Filter Size

1

4 10 x 16

2

2 20 x 25

3

4 15 X 20

4

4 18 X 25

5

9 14.5 x 19

Vertical Filters

Unit Size

Filter Quantity

Filter Size

1

1 10 x 16

2

1 16 x 25

3

2 15 x 15

4

2 16 x 20

5

3 14.5 x 19

Yearly

1. Before each heating season, verify that the drain on the bottom of each common flue box of every

furnace in the unit is clear.

2. Inspect bearings for wear and deterioration. Replace if necessary.
3. Inspect belt wear and replace torn or worn belts.
4. Inspect bolts and set screws for tightness. Tighten as necessary.
5. Inspect motor for cleanliness. Clean exterior surfaces only. Remove dust and grease from the

motor housing to ensure proper motor cooling. Remove dirt and grease from the wheel and
housing to prevent imbalance and damage.

6. The heat exchanger should be checked for cracks. The heat exchanger should be replaced

immediately if cracks are detected.

7. Inspect the combustion blower motor for cleanliness. Clean exterior surfaces of the combustion

blower motor only. Removing excess dust and grease guarantees proper motor cooling.

8. Before each heating season, examine the burner and gas orifices. Inspect burner ports for

foreign debris, heat exchanger, and spark igniter for cleanliness.