Remote panel troubleshooting chart – FloAire INDIRECT FIRED BENT TUBE MODULE User Manual

Page 36

Advertising
background image

36

Remote Panel Troubleshooting Chart

Light Indication

Condition

Possible Cause

No Lights

Power not available to Remote Panel

Bad voltage to unit

Main disconnect in “OFF” Position

Circuit breaker tripped

Bad main transformer

POWER Light Only

Proper unit Off Operation

No problem

No power to motor starter

Blower On/Blower Off Switch in “Blower

Off” Position

Improper damper function

Low Temperature Thermostat Timed

Out (Option)

Improper Airflow

Insufficient Airflow
Bad airflow switch

Problem with air probes

Problem with airflow tubing

Broken Belt

POWER Light and
BLOWER ON Light

Proper Ventilation Operation

No Problem

No Power to Flame Safety Controller

Heat/Vent Switch in “Vent” Position

Gas Pressure Switch Tripped (option)

High Temperature Limit Thermostat

Tripped

CLOGGED FILTER Light On
(Optional)

Filters Clogged

Filters Dirty or Need Replacement

LOW TEMP Light On
(Optional)

Freeze-stat has shut blower down

Discharge Temperature Too Cold

Heating System is not Functioning

POWER Light and
BLOWER ON Light and
HEAT ON Light

Proper Heating Operation

No Problem