25h b b /25h b c – FloAire 25HBC User Manual

Page 8

Advertising
background image

8

Table 5 – Required Liquid Line Temperatures _F

LIQUID PRESSURE AT

SERVICE VALVE (PSIG)

REQUIRED SUBCOOLING TEMPERATURE (° F)

8

10

12

14

16

18

251

76

74

72

70

68

66

259

78

76

74

72

70

68

266

80

78

76

74

72

70

274

82

80

78

76

74

72

283

84

82

80

78

76

74

291

86

84

82

80

78

76

299

88

86

84

82

80

78

308

90

88

86

84

82

80

317

92

90

88

86

84

82

326

94

92

90

88

86

84

335

96

94

92

90

88

86

345

98

96

94

92

90

88

354

100

98

96

94

92

90

364

102

100

98

96

94

92

374

104

102

100

98

96

94

384

106

104

102

100

98

96

395

108

106

104

102

100

98

406

110

108

106

104

102

100

416

112

110

108

106

104

102

427

114

112

110

108

106

104

439

116

114

112

110

108

106

450

118

116

114

112

110

108

462

120

118

116

114

112

110

474

122

120

118

116

114

112

486

124

122

120

118

116

114

499

126

124

122

120

118

116

511

128

126

124

122

120

118

Table 6 – Superheat Charging (Heat Pump Only)

OUTDOOR TEMP (° F)

EVAPORATOR ENTERING AIR TEMPERATURE (° F WB)

50

52

54

56

58

60

62

64

67

68

70

72

74

76

55

11

11

12

12

12

13

17

20

24

24

25

25

25

25

60

6

6

7

7

7

7

12

16

21

22

23

23

23

23

65

---

---

---

---

---

3

7

12

18

19

21

21

22

22

70

---

---

---

---

---

---

---

7

14

16

18

20

20

20

75

---

---

---

---

---

---

---

3

11

13

16

18

18

19

82

---

---

---

---

---

---

---

---

*6

8

12

15

16

17

85

---

---

---

---

---

---

---

---

4

7

11

14

15

16

90

---

---

---

---

---

---

---

---

---

4

8

12

14

15

95

---

---

---

---

---

---

---

---

---

---

6

10

12

14

100

---

---

---

---

---

---

---

---

---

---

4

8

11

12

105

---

---

---

---

---

---

---

---

---

---

3

6

9

11

110

---

---

---

---

---

---

---

---

---

---

---

5

7

10

115

---

---

---

---

---

---

---

---

---

---

---

3

6

8

*Optimum performance point, 82 ° F outdoor ambient and (80 ° F dry bulb),( 67 ° F wet bulb) indoor conditions. (DOE B Test Conditions)
Where a dash (--- ---) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.

Note: Superheat ° F is at low---side service port, Allow a tolerance of ± 3 ° F
Note: Indoor dry bulb between 70 ° F and 80 ° F

Table 7 – Required Suction--Line Temperature

SUPERHEAT TEMP

˚F)

SUCTION PRESSURE AT SERVICE PORT (PSIG)

107.8

112.2

116.8

121.2

126

130.8

138.8

140.8

145.8

0

35

37

39

41

43

45

47

49

51

2

37

39

41

43

45

47

49

51

53

4

39

41

43

45

47

49

51

53

55

6

41

43

45

47

49

51

53

55

57

8

43

45

47

49

51

53

55

57

59

10

45

47

49

51

53

55

57

59

61

12

47

49

51

53

55

57

59

61

63

14

49

51

53

55

57

59

61

63

65

16

51

53

55

57

59

61

63

65

67

18

53

55

57

59

61

63

65

67

69

20

55

57

59

61

63

65

67

69

71

22

57

59

61

63

65

67

69

71

73

24

59

61

63

65

67

69

71

73

75

26

61

63

65

67

69

71

73

75

77

28

63

65

67

69

71

73

75

77

79

30

65

67

69

71

73

75

77

79

81

25H

B

B

/25H

B

C

Advertising
This manual is related to the following products: