Optional Moisture Eliminator Panel

If the unit is equipped with an optional moisture eliminator panel, the maximum face velocity of the coil
may be increased to 650 FPM. Moisture eliminator panels require minimal maintenance. Visual
inspection is recommended periodically. Scale or clogging will impair performance. If scale or clogging
occurs, remove the panel and flush with steam or water. Flushing should not have sufficient force to
dislodge the media from the panel. Scale removal may require a vinegar or detergent application
followed by rinsing