Electrical – FloAire Direct Expansion Coil Modules User Manual

Page 11

Advertising
background image

11

Copper Wire Ampacity

Wire Size AWG

Maximum Amps

14

20

12

25

10

30

8

40

6

55

4

70

3

85

2

95

1

110

0

125

00

145

Electrical

Before connecting power to the module, read and understand
the entire section of this document. As-built wiring diagrams
are furnished with each module by the factory, and are
attached either to the door of the unit or provided with a
paperwork packet.

Electrical wiring and connections should be done in
accordance with local ordnances and the National Electric
Code, ANSI/NFPA70. Be sure the voltage and phase of the
power supply and the wire amperage capacity is in accordance
with the unit nameplate. For additional safety
information refer to AMCA publication 410-96, Recommended
Safety Practices for Users and Installers of Industrial and
Commercial Fans.

1. Always disconnect power before working on or near

this equipment. Lock and tag the disconnect switch or
breaker to prevent accidental power up.

2. Make certain that the power source is compatible with

the requirements of your equipment. The Air handler
wiring schematic and the compressor documentation
identifies the proper phase and voltage of the
equipment.

3. Secure the power cable to prevent contact with sharp

objects.

4. Do not kink power cable and never allow the cable to

come in contact with oil, water, grease, hot surfaces or
chemicals.

5. There are RC, Y1, and Y2 terminals for cooling in the

electrical control package or heated make up air. These terminals must be connected to the
matching terminals in the condenser.

6. Before powering up the DX module and compressing unit, make sure that the interior of the unit is

free of loose debris or shipping materials, and all refrigerant piping is complete.

WARNING!!

Disconnect

power

before

installing or servicing module.
High voltage electrical input is
needed for this equipment. This
work should be performed by a
qualified electrician.

Dry Contacts for Condensing Unit.

Located in Pre-wire or Heated Make-

up-air unit.

Terminals on Condensing Unit

Stage Y1 connects to Terminal Y1
in Heater or Electrical Package

Stage Y2 connects to Terminal Y2
in Heater or Electrical Package

Connect to Terminal RC in Heater
or Electrical Package

Advertising