Troubleshooting – FloAire Direct Expansion Coil Modules User Manual

Page 14

Advertising
background image

14

Troubleshooting

The following table lists causes and corrective actions for possible problems with DX coil modules.
Review this list prior to consulting manufacturer.

Troubleshooting Chart

* Air velocity should be maintained between 200 and 550 FT per Minute through the coil.

Problem

Potential Cause

Corrective Action

Insufficient Cooling

Frozen coil

Reduce refrigerant charge.
Check for proper airflow across
coil.

Charge is low

Add refrigerant charge.

Excessive air flow

Slow blower RPM down.

Contaminated refrigerant

Have refrigerant replaced.

Frozen coil

Reduce refrigerant charge.

Insufficient Airflow


Coil sized too small *

Increase airflow across coil.
Replace module with larger coil.

Overestimation of static pressure

Reduce blower rpm.

Excessive Airflow


Coil sized too large *

Change motor HP.
Slow blower RPM down.

Excessive airflow

Slow blower RPM down.

Water in ductwork

Drip pan full

Check drip pan for obstructions.


Ductwork is not insulated

Check drip pan plumbing for
clogs.
Insulate ductwork to reduce
condensation.