Framing the Ceiling Hole

Frame the ceiling chimney hole as shown in Figure 13.
It is good practice to use framing lumber that is the
same size as the ceiling joists; this is a requirement at
attic level.
The following table gives firestop spacer model num-
bers:

Safety strips are used to ensure that any combustible
materials in front of the fireplace are protected even
though a noncombustible hearth extension is required.
If fireplace is to be elevated above the floor, a “Z”
shaped metal safety strip must be fabricated and used
to protect combustible surfaces in front of the fireplace.
This “Z” shaped safety strip is not provided but must be
fabricated of metal with each horizontal leg at least 1¹⁄₂"
(38 mm) wide and equal in length to the metal strips
provided with the fireplace.
Note: Safety strips are not required over noncombus-
tible floors where all supports at the base of the fireplace
are noncombustible.
Four (4) nailing flanges are supplied with the fireplace
(found on the fireplace hearth). To level the box and
secure it firmly in place, remove the nailing flanges from
the hearth and install at the sides of the fireplace as
shown in Figure 15.

Fig. 13 Typical frame for ceiling chimney hole.

FP551

WF551

BR/BC

9/29/97

See
Fig. 12

See
Fig. 12

Existing

Ceiling

Joists

Ceiling

New Framing

Members

Chimney

Hole

Fig. 12 Ceiling chimney hole sizes necessary for installing

firestop spacer.

Size of Chimney

Vertical

30°

8" Flue

SKFS2A

SKFS6A

"SK" Series

14¹⁄₂" x 14¹⁄₂"

14¹⁄₂" x 25¹⁄₂"

(368mm x 368mm) (368mm x 648mm)

8" Flue

FS2A

FS6A

"S" Series 3-Wall

17¹⁄₂" x 17¹⁄₂"

17⁷⁄₈" x 29⁵⁄₈"

(445mm x 445mm) (454mm x 753mm)

Angle of Chimney at Ceiling

The inside dimension of the frame must be the same
as the hole size selected from Figure 13 in order
to provide required air space between the outside
diameter of the chimney and the edges of the framed
ceiling hole. (1¹⁄₂" - SK8; 2" - 3 wall)

Positioning, Safety Strips,

Securing The Fireplace

Slide fireplace into position.
Lift the fireplace front slightly and slide the metal safety
strips under front bottom edge about 1¹⁄₂" (38 mm),
allowing the remainder to extend in front of firebox.
Overlap strips at least 1/2" (13 mm) to provide a posi-
tive joint. (Flat safety strips are packed with fireplace.)
(Fig. 14)

FPC557

Fig. 14 Safety strip installation.

FPC557

WMC Safety strip installation

circulatin models

1/29/99 djt

Metal Safety

Strips

(1, 2 or 3 Pieces)

¹⁄₂

" (13mm)

Min. Overlap

1¹⁄₂

"

(38mm)

"Z"

Safety

Strip

Fire-

Place

Plat-

Form

Hearth Ext.

(not supplied)

FPC549

Fig. 15 Fasten fireplace in position.

FPC549

Nail flange/standoff

circulating models

1/29/99 djt

Nail Top

Standoffs

Nail Side-

Nailing

Flanges

Advertising