WMC Series Woodburning Fireplace

20000583

Hearth Installation

A hearth extension is required to protect a combustible
floor in front of the fireplace. Refer to Figure 24 for
minimum dimensions and mounting detail.
NOTE: Hearth Extension must not cover the air
inlet/outlet opening of a fireplace.
The hearth extension described in Figure 24 must be a
durable noncombustible material with a minimum (to-
tal) Rt value of 1.09; refer to Figure 25 for examples.
The overall height (above a combustible floor), depth
and width must be as indicated, with the extension
centered to the fireplace opening.
The top of insulation must be covered with a noncom-
bustible decorative covering or a piece of .018” mini-
mum sheet metal, to protect hearth extension material.
(Fig. 24)

Secure the hearth extension to the floor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges. Seal crack between the fire-
place hearth and hearth extension with a noncombus-
tible material. (Figs. 22 and 26)

WARNING: HEARTH EXTENSION MUST BE IN-
STALLED IN ACCORDANCE WITH FIGURE 24 AND
MUST NOT COVER THE BOTTOM FRONT OPENING
OF THE CIRCULATING MODEL.
Alternate noncombustible materials may be used provid-
ing the (total) thermal resistance (Rt value) of the alter-
nate material employed is greater than or equal to R =
1.09. Thermal resistance (R) or thermal conductivity (K),
may be obtained from manufacturer of the material. Fac-
tors are related by the formula K = 1/R.
T = given thickness
R = thermal resistance for a given thickness (T)
K = thermal conductivity
Noncombustible material with a lower R value may
be used, provided thickness of material is sufficiently
greater to maintain an equivalent (total) thermal resis-
tance (Rt).

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the

fireplace

and hearth

extension with

noncombustible

material

Safety strips

must overlap

���

" minimum

May install

noncombustible

decorative

covering

OR .018" min.

sheet metal

FIREPLACE

HEARTH

COMBUSTIBLE

FLOOR

MINIMUM

INSULATION

VALUE "R"

4" MIN.

FP594A
WMC combustible min.
1/29/99 djt

FIREBOX

OPENING

A - Min. clearance

to combustible

perpendicular wall

B - Min. clearance

to combustible

perpendicular wall when

using noncombustible wall shield*

SIDE

WALL

SIDE

WALL

F**

C**

E

E

D

4" BRICK

(Example material)

Combustible material permitted within shaded area.

* Noncombustible wall shield requires 1" Majestic EH2416

insulation (minimum R Value = 1.85) between decorative

noncombustible rigid covering and combustible wall.

Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness

of noncombustible surround facing.

4"

Shaded area starts

1/2" away from

edge of unit

FP594A

Fig. 24 Combustible side wall protection and hearth extension dimensions.

A

B

C

D

E

F

G

H

J

WMC36

16"

12"

48°

41°

18"

14"

7³⁄₄"

16"

48"

406 mm 305 mm

457 mm 356 mm 197 mm 406 mm 1219 mm

WMC42

20"

12"

42°

35°

18"

14"

11¹⁄₂"

20"

61¹⁄₂"

508 mm 305 mm

457 mm 356 mm 292 mm 508 mm 1562 mm