WMC Series Woodburning Fireplace

20000583

D

RISE

B

G

H

B

OFFSET

C

E

6 FT.

G

H

A

HEARTH

FLOOR

CHIMNEY

SECTION

CHIMNEY FLUE EXIT

ELBOW

FPC269

Chimney Requirements -typ. offset

Circulating models

1/28/99 djt

30˚

OFFSET

ELBOW

30˚

OFFSET

ELBOW

30˚

RETURN

ELBOW

30˚

RETURN

ELBOW

SKCS8

SUPPORT

Example 1

Example 2

Example 3

Chimney Requirements - Offset Installations

30˚ Elbow Offsets

1' 1¹⁄₂' 3' 4'

Offset

Rise

Illustration Key

The following safety rules apply to
offset installations (letters correspond
with illustration above):
A. Height of the chimney is measured
from the hearth to the chimney exit.

WMC36 WMC42

Maximum:

90'

90'

Minimum:
Without Elbows 12' 6"

12' 6"

With 2 Elbows* 15' 0"

15' 0"

With 4 Elbows* 21' 0"

21' 0"

B. Do not use more than 4 elbows per
chimney.
Attach the straps of the return (top)
elbow to a structural framing member.
The offset (first) elbow of any pair does
not have straps.

FPC269

IWF282

MBUF

5/26/96

OFFSET

RISE

IWF282

* In Canada, two (2) SK845 are allowed.

Fig. 4 Chimney system requirements.

Chimney

Support

0 0 0 0 0

3"

11"

1 0 0 0 0

8¹⁄₄"

20"

0 1 0 0 0 11¹⁄₄" 25¹⁄₄"
2 0 0 0 0 13¹⁄₂" 29¹⁄₄"
1 1 0 0 0 16¹⁄₂" 34¹⁄₄"
0 0 1 0 0 20¹⁄₄" 40³⁄₄"
2 1 0 0 0 21³⁄₄" 43¹⁄₂"
0 0 0 1 0 26¹⁄₄" 51¹⁄₄"
0 1 1 0 0 28¹⁄₂" 55¹⁄₄"
1 0 0 1 0 31¹⁄₂" 60¹⁄₄”
0 1 0 1 0 34¹⁄₂" 65¹⁄₂"
0 0 2 0 0 37¹⁄₂" 70³⁄₄"
1 1 0 1 1 41¹⁄₂" 77³⁄₄"
0 0 1 1 1

45" 83³⁄₄"

0 1 2 0 1 47¹⁄₄" 87¹⁄₂"
0 0 0 2 1

51"

94"

0 1 1 1 1 53¹⁄₄"

98"

0 0 3 0 1 56¹⁄₄" 103¹⁄₄"
0 1 0 2 1 59¹⁄₄" 108¹⁄₂"
0 0 2 1 1 62¹⁄₄" 113¹⁄₂"
0 1 3 0 1 64¹⁄₂" 117¹⁄₂"
0 0 1 2 1 68¹⁄₄" 124"
0 1 2 1 1 70¹⁄₂" 128"
0 0 0 3 1 74¹⁄₄" 134¹⁄₂"
0 1 1 2 2

78" 140³⁄₄"

0 0 3 1 2

81" 146"

0 1 0 3 2

84" 151¹⁄₄"

0 0 2 2 2

87" 156¹⁄₂"

0 1 3 1 2 89¹⁄₄" 160¹⁄₄"
0 0 1 3 2

93" 166³⁄₄"

0 1 2 2 2 95¹⁄₄" 170³⁄₄"
0 0 0 4 2 99¹⁄₄" 177³⁄₄"
0 1 1 3 2 101¹⁄₄" 181³⁄₄"
0 0 3 2 2 104¹⁄₄" 186¹⁄₄"
0 1 0 4 2 107¹⁄₄" 191¹⁄₂"
0 0 2 3 2 110¹⁄₄" 196³⁄₄"
0 1 3 2 3

114" 203¹⁄₄"

0 0 1 4 3 117³⁄₄" 209³⁄₄"
0 1 2 3 3

120" 213¹⁄₂"

0 0 0 5 3 123³⁄₄" 220"

C. The chimney cannot be more than 30˚
(45˚ in Canada) from the vertical plane in
any installation*.
D. The maximum length of the angled run
of the total chimney system is 20 feet. (G
plus H cannot exceed 20 feet.)
E. A chimney support (Model SKCS8,
TCS8A - 8 inch triple wall) is required
every 6 feet of angled run of chimney.
Chimney supports are required for every
30 feet and 60 feet (SK8 pipe) or 20 feet
and 40 feet (3-wall pipe) of vertical chim-
ney height above the hearth.
Determine the offset distance of your
chimney arrangement from the centerline
of the fireplace to the centerline of the
chimney where it is to pass through the
first ceiling.

NOTE: This offset distance may not be
your full offset distance. See Examples 2
and 3.

Notes: G + H cannot exceed 20 feet.

Air Space Clearances: SK8 (2-wall) = 1¹⁄₂" and "S" Series (3-wall) = 2"