Wmc series woodburning fireplace, Installing outside air kit, Installing the chimney system – CFM Corporation WMC36 WMC42 User Manual

Page 11: Installing the firestop spacer in the ceiling hole, Proper firestop spacer installation

Advertising
background image

11

WMC Series Woodburning Fireplace

20000583

Installing Outside Air Kit

An outside air kit is installed in all WMC Series Fire-
places. If desired, or if local codes mandate the use of
an air kit, then an AK-MST is required to complete the
installation (from air kit to the outdoors). If the outside
air kit is to be used, the AK-MST MUST be installed
BEFORE the fireplace is enclosed. Refer to the AK-
MST instructions for field installation. The outside air
control lever is located at the front edge of the left side
brick. To ‘open’, push the control lever down toward
the hearth brick. To ‘close’, pull the control lever up
and over. (Fig. 16)

FPC558

Fig. 17 Install pipe, listening for the snap-lock to fasten.

UP

FPC558

WMC

Pipe install

Circulating models

1/29/99 djt

Inner Pipe Section

Pipe

Rim

Pipe

Rim

Hem

Lance

FP270/271

CR Series

2/19/99 djt

Elbow Strap

Angled Strap

Fig. 18 Attach straps to a structural framing member.

FP270/271

Support Structure

Elbow Strap

(Must be tight)

Ceiling

Hole

Framing

Angle Firestop

Chimney Support Strap

(Must be tight)

CLOSED

OPEN

WF 710

OUTSIDE AIR LEVER

WOOD FIREPLACES

5/28/98

FP710

Fig. 16 Outside air operation.

Installing the Chimney System

Start by attaching the first chimney section to the collar
on top of the fireplace.
Install the pipe as pictured in Figure 17. When you
get a good lock, you will hear the pipe clearly snap
together. Once sections are snap-locked in place, it is
extremely difficult to get them apart. Make sure the
pipe is firmly snapped and locked together as each
pipe section is mounted.
When installing elbows, only outer pipe will snap- lock.
Middle pipes simply slide into position. Be sure to
always attach straps on upper elbow to a structural
framing member. (Fig. 18)
Continue installing the pipe as required until pipe is
installed up through the ceiling. At this point, you must
install a firestop spacer.

Installing the Firestop Spacer

in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly
and required for safety.
Nail the firestop spacer (at each corner) to the framing
members of the ceiling hole. NOTE: A firestop spacer
is not required at the roof.

Hole sizes listed in Figure 13 for angled firestop spacers
provide minimum required air space to chimney pipe for
ceiling thickness up to 8" (203 mm). When combined
thickness of ceiling material, ceiling joists and flooring
material exceeds 8" (203 mm), adjustments must be
made in framing to assure that minimum air spaces to
chimney are maintained.

Proper Firestop Spacer Installation

Figure 19 shows different installation procedures for
both an area that is an attic and an area that is not an
attic.
If the area above the ceiling is not an attic, position the
firestop spacer with the flange on the ceiling side and the
angled portion extending up into the hole.
If the area above the ceiling is an attic, position the
firestop spacer with the flange on the top of the framed

Advertising