Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR User Manual
Page 11
Table 7 — 19XR Additional Data for Marine Waterboxes*
HEAT EXCHANGER
FRAME, PASS
ENGLISH
SI
Psig
Rigging Weight
(lb)
Water Volume
(gal)
kPa
Rigging Weight
(kg)
Water Volume
(L)
FRAME 2, 1 AND 2 PASS
150
730
84
1034
331
318
FRAME 2, 2 PASS
150
365
42
1034
166
159
FRAME 3, 1 AND 2 PASS
150
730
84
1034
331
317
FRAME 3, 2 PASS
150
365
42
1034
166
159
FRAME 4, 1 AND 3 PASS
150
1060
123
1034
481
465
FRAME 4, 2 PASS
150
530
61
1034
240
231
FRAME 5, 1 AND 3 PASS
150
1240
139
1034
562
526
FRAME 5, 2 PASS
150
620
69
1034
281
263
FRAME 6, 1 AND 3 PASS
150
1500
162
1034
680
612
FRAME 6, 2 PASS
150
750
81
1034
340
306
FRAME 7, 1 AND 3 PASS
150
2010
326
1034
912
1234
FRAME 7, 2 PASS
150
740
163
1034
336
617
FRAME 8, 1 AND 3 PASS
150
1855
406
1034
841
1537
FRAME 8, 2 PASS
150
585
203
1034
265
768
FRAME 2, 1 AND 3 PASS
300
860
84
2068
390
318
FRAME 2, 2 PASS
300
430
42
2068
195
159
FRAME 3, 1 AND 3 PASS
300
860
84
2068
390
317
FRAME 3, 2 PASS
300
430
42
2068
195
159
FRAME 4, 1 AND 3 PASS
300
1210
123
2068
549
465
FRAME 4, 2 PASS
300
600
61
2068
272
231
FRAME 5, 1 AND 3 PASS
300
1380
139
2068
626
526
FRAME 5, 2 PASS
300
690
69
2068
313
263
FRAME 6, 1 AND 3 PASS
300
1650
162
2068
748
612
FRAME 6, 2 PASS
300
825
81
2068
374
306
FRAME 7, 1 AND 3 PASS
300
3100
326
2068
1406
1234
FRAME 7, 2 PASS
300
2295
163
2068
1041
617
FRAME 8, 1 AND 3 PASS
300
2745
405
2068
1245
1533
FRAME 8, 2 PASS
300
1630
203
2068
739
768
*Add to heat exchanger data for total weights or volumes.
NOTES:
1. Weight adder shown is the same for cooler and condenser of equal frame size.
2. For the total weight of a vessel with a marine waterbox, add these values to the heat
exchanger weights (or volumes).
11