Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR User Manual

Page 24

Advertising
background image

Table 9 — 19XR Waterbox Nozzle Sizes

FRAME

SIZE

PRESSURE

psig (kPa)

PASS

NOMINAL PIPE SIZE (in.)

ACTUAL PIPE ID (in.)

Cooler

Condenser

Cooler

Condenser

1

150/300

(1034/2068)

1

8

8

7.981

7.981

2

6

6

6.065

6.065

3

6

6

6.065

6.065

2

150/300

(1034/2068)

1

10

10

10.020

10.020

2

8

8

7.981

7.981

3

6

6

6.065

6.065

3

150/300

(1034/2068)

1

10

10

10.020

10.020

2

8

8

7.981

7.981

3

6

6

6.065

6.065

4

150/300

(1034/2068)

1

10

10

10.020

10.020

2

8

8

7.981

7.981

3

6

6

6.065

6.065

5

150/300

(1034/2068)

1

10

10

10.020

10.020

2

8

10

7.981

10.020

3

6

8

6.065

7.981

6

150/300

(1034/2068)

1

10

10

10.020

10.020

2

10

10

10.020

10.020

3

8

8

7.981

7.981

7

150

(1034)

1

14

14

13.250

13.250

2

12

12

12.000

12.000

3

10

12

10.020

12.000

300

(2068)

1

14

14

12.500

12.500

2

12

12

11.376

11.750

3

10

12

9.750

11.750

8

150

(1034)

1

14

14

13.250

13.250

2

14

14

13.250

13.250

3

12

12

12.000

12.000

300

(2068)

1

14

14

12.500

12.500

2

14

14

12.500

12.500

3

12

12

11.376

11.376

24