Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR User Manual

Page 12

Advertising
background image

Table 8A — 19XR Waterbox Cover Weights

ENGLISH (lb)

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 1

FRAME 2

FRAME 3

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/
CONDENSER

NIH, 1 Pass Cover, 150 psig

177

204

320

350

320

350

NIH, 2 Pass Cover, 150 psig

185

218

320

350

320

350

NIH, 3 Pass Cover, 150 psig

180

196

300

340

300

340

NIH/MWB End Cover, 150 psig

136

136

300

300

300

300

NIH, 1 Pass Cover, 300 psig

248

301

411

486

411

486

NIH, 2 Pass Cover, 300 psig

255

324

411

518

411

518

NIH, 3 Pass Cover, 300 psig

253

288

433

468

433

468

NIH/MWB End Cover, 300 psig

175

175

400

400

400

400

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 4

FRAME 5

FRAME 6

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/
CONDENSER

NIH, 1 Pass Cover, 150 psig

485

521

616

652

802

838

NIH, 2 Pass Cover, 150 psig

487

540

590

663

770

843

NIH, 3 Pass Cover, 150 psig

504

520

629

655

817

843

NIH/MWB End Cover, 150 psig

379

379

428

428

583

583

NIH, 1 Pass Cover, 300 psig

593

668

764

655

880

956

NIH, 2 Pass Cover, 300 psig

594

700

761

839

844

995

NIH, 3 Pass Cover, 300 psig

621

656

795

838

901

952

NIH/MWB End Cover, 300 psig

569

569

713

713

833

833

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 7 COOLER

FRAME 7 CONDENSER

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/
CONDENSER

NIH, 1 Pass Cover, 150 psig

1392

1469

1205

1282

NIH, 2 Pass Cover, 150 psig

1345

1461

1163

1279

NIH, 3 Pass Cover, 150 psig

1434

1471

1222

1280

NIH/MWB End Cover, 150 psig

1022

1022

920

920

NIH, 1 Pass Cover, 300 psig

1985

2150

1690

1851

NIH, 2 Pass Cover, 300 psig

1934

2174

1628

1862

NIH, 3 Pass Cover, 300 psig

2009

2090

1714

1831

NIH/MWB End Cover, 300 psig

1567

1567

1923

1923

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 8 COOLER

FRAME 8 CONDENSER

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/
CONDENSER

NIH, 1 Pass Cover, 150 psig

1831

1909

1682

1760

NIH, 2 Pass Cover, 150 psig

1739

1893

1589

1744

NIH, 3 Pass Cover, 150 psig

1851

1909

1702

1761

NIH/MWB End Cover, 150 psig

1480

1480

1228

1228

NIH, 1 Pass Cover, 300 psig

2690

2854

2394

2549

NIH, 2 Pass Cover, 300 psig

2595

2924

2269

2578

NIH, 3 Pass Cover, 300 psig

2698

2861

2417

2529

NIH/MWB End Cover, 300 psig

1440

1440

1767

1767

LEGEND

NIH

Nozzle-in-Head

MWB — Marine Waterbox

NOTE: Weight for NIH 2-Pass Cover, 150 psig is included in the heat exchanger weights shown in Table 6.

RIG MACHINE COMPONENTS — Refer to instructions
below, Fig. 6-9, and Carrier Certified Prints for machine com-
ponent disassembly.

IMPORTANT: Only a qualified service technician should
perform this operation.

Do not attempt to disconnect flanges while the machine
is under pressure. Failure to relieve pressure can result
in personal injury or damage to the unit.

Before rigging the compressor, disconnect all wires en-
tering the power panel.

12

Advertising