Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR User Manual
Page 9
Table 4 — 19XR Compressor Weights
MOTOR
CODE
ENGLISH
SI
Total Compressor Weight*
(lb)
Total Compressor Weight*
(kg)
60 Hz
50 Hz
60 Hz
50 Hz
BD
3,755
3,755
1703
1703
BE
3,805
3,805
1726
1726
BF
3,870
3,870
1755
1755
BG
3,950
3,950
1792
1792
BH
3,950
3,950
1792
1792
CD
4,659
4,756
2134
2153
CE
4,685
4,771
2155
2165
CL
4,710
4,842
2137
2167
CM
4,737
4,868
2149
2209
CN
4,751
4,883
2156
2215
CP
4,806
4,898
2181
2212
CQ
4,874
4,898
2211
2212
DB
6,112
6,158
2772
2793
DC
6,138
6,224
2822
2823
DD
6,216
6,262
2819
2840
DE
6,224
6,351
2823
2881
DF
6,274
6,412
2846
2908
DG
6,364
6,466
2886
2933
DH
6,412
6,868
2908
3115
DJ
6,466
6,977
2933
3165
EH
8,025
11,135
3640
5051
EJ
11,085
11,265
5028
5110
EK
11,160
11,282
5062
5118
EL
11,181
11,435
5072
5187
EM
11,271
11,435
5113
5187
EN
11,335
11,635
5142
5278
EP
11,434
11,605
5186
5264
*Compressor weight is comprised of compressor, stator, rotor, end bell, suction elbow, and dis-
charge elbow.
NOTE: For medium voltage motors (over 600 v), add 490 lb (222 kg).
Table 5 — 19XR Component Weights
COMPONENT
FRAME 2
COMPRESSOR
FRAME 3
COMPRESSOR
FRAME 4
COMPRESSOR
FRAME 5
COMPRESSOR
lb
kg
lb
kg
lb
kg
lb
kg
Suction Elbow
50
23
54
24
175
79
210
95
Discharge Elbow
60
27
46
21
157
71
140
63
Control Cabinet*
30
14
30
14
30
14
30
14
Optional Unit-Mounted Starter†
800
363
800
363
800
363
800
363
Optional Isolation Valves
115
52
115
52
115
52
115
52
*Included in total cooler weight.
†Weight of optional factory-mounted starter is not included and must be added to the heat
exchanger weight.
9