Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR User Manual
Page 13
Table 8B — 19XR Waterbox Cover Weights
SI (kg)
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 1
FRAME 2
FRAME 3
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/
CONDENSER
NIH, 1 Pass Cover, 150 psig
80
93
145
159
145
159
NIH, 2 Pass Cover, 150 psig
84
99
145
159
145
159
NIH, 3 Pass Cover, 150 psig
82
89
136
154
140
154
NIH/MWB End Cover, 150 psig
62
62
136
136
136
136
NIH, 1 Pass Cover, 300 psig
112
137
186
220
186
220
NIH, 2 Pass Cover, 300 psig
116
147
186
235
186
235
NIH, 3 Pass Cover, 300 psig
115
131
196
212
196
212
NIH/MWB End Cover, 300 psig
79
79
181
181
181
181
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 4
FRAME 5
FRAME 6
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/
CONDENSER
NIH, 1 Pass Cover, 150 psig
220
236
279
296
364
380
NIH, 2 Pass Cover, 150 psig
221
245
268
301
349
382
NIH, 3 Pass Cover, 150 psig
229
236
285
297
371
381
NIH/MWB End Cover, 150 psig
172
172
194
194
265
265
NIH, 1 Pass Cover, 300 psig
269
303
347
381
399
434
NIH, 2 Pass Cover, 300 psig
269
318
345
398
383
451
NIH, 3 Pass Cover, 300 psig
282
298
361
380
409
432
NIH/MWB End Cover, 300 psig
258
258
323
323
378
378
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 7 COOLER
FRAME 7 CONDENSER
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/
CONDENSER
NIH, 1 Pass Cover, 150 psig
631
666
547
582
NIH, 2 Pass Cover, 150 psig
610
663
528
580
NIH, 3 Pass Cover, 150 psig
650
667
554
581
NIH/MWB End Cover, 150 psig
464
464
417
417
NIH, 1 Pass Cover, 300 psig
900
975
767
840
NIH, 2 Pass Cover, 300 psig
877
986
738
845
NIH, 3 Pass Cover, 300 psig
911
948
777
831
NIH/MWB End Cover, 300 psig
711
711
872
872
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 8 COOLER
FRAME 8 CONDENSER
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/
CONDENSER
NIH, 1 Pass Cover, 150 psig
831
866
763
798
NIH, 2 Pass Cover, 150 psig
789
859
721
791
NIH, 3 Pass Cover, 150 psig
840
866
772
799
NIH/MWB End Cover, 150 psig
671
671
557
557
NIH, 1 Pass Cover, 300 psig
1220
1295
1086
1156
NIH, 2 Pass Cover, 300 psig
1177
1326
1029
1169
NIH, 3 Pass Cover, 300 psig
1224
1298
1096
1147
NIH/MWB End Cover, 300 psig
653
653
802
802
LEGEND
NIH
— Nozzle-in-Head
MWB — Marine Waterbox
NOTE: Weight for NIH 2-Pass Cover, 150 psig is included in the heat exchanger weights shown in Table 6.
NOTE: If the cooler and condenser vessels must be sepa-
rated, the heat exchangers should be kept level by placing a
support plate under the tube sheets. The support plate will
also help to keep the vessels level and aligned when the ves-
sels are bolted back together.
NOTE: Wiring must also be disconnected. Label each wire
before removal (see Carrier Certified Prints). In order to dis-
connect the starter from the machine, remove wiring for the
oil pump, oil heater, control wiring at the power panel, and
the main motor leads at the starter lugs.
Remove all transducer and sensor wires at the sensor. Clip
all wire ties necessary to pull heat exchangers apart.
To Separate Cooler and Condenser:
1. Place a support plate under each tube sheet to keep each
vessel level (Fig. 6, Item 6).
2. Cut the refrigerant motor cooling line at the location shown
(Fig. 6, Item 7).
13