Table 8B — 19XR Waterbox Cover Weights

SI (kg)

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 1

FRAME 2

FRAME 3

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/
CONDENSER

NIH, 1 Pass Cover, 150 psig

80

93

145

159

145

159

NIH, 2 Pass Cover, 150 psig

84

99

145

159

145

159

NIH, 3 Pass Cover, 150 psig

82

89

136

154

140

154

NIH/MWB End Cover, 150 psig

62

62

136

136

136

136

NIH, 1 Pass Cover, 300 psig

112

137

186

220

186

220

NIH, 2 Pass Cover, 300 psig

116

147

186

235

186

235

NIH, 3 Pass Cover, 300 psig

115

131

196

212

196

212

NIH/MWB End Cover, 300 psig

79

79

181

181

181

181

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 4

FRAME 5

FRAME 6

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/
CONDENSER

NIH, 1 Pass Cover, 150 psig

220

236

279

296

364

380

NIH, 2 Pass Cover, 150 psig

221

245

268

301

349

382

NIH, 3 Pass Cover, 150 psig

229

236

285

297

371

381

NIH/MWB End Cover, 150 psig

172

172

194

194

265

265

NIH, 1 Pass Cover, 300 psig

269

303

347

381

399

434

NIH, 2 Pass Cover, 300 psig

269

318

345

398

383

451

NIH, 3 Pass Cover, 300 psig

282

298

361

380

409

432

NIH/MWB End Cover, 300 psig

258

258

323

323

378

378

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 7 COOLER

FRAME 7 CONDENSER

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/
CONDENSER

NIH, 1 Pass Cover, 150 psig

631

666

547

582

NIH, 2 Pass Cover, 150 psig

610

663

528

580

NIH, 3 Pass Cover, 150 psig

650

667

554

581

NIH/MWB End Cover, 150 psig

464

464

417

417

NIH, 1 Pass Cover, 300 psig

900

975

767

840

NIH, 2 Pass Cover, 300 psig

877

986

738

845

NIH, 3 Pass Cover, 300 psig

911

948

777

831

NIH/MWB End Cover, 300 psig

711

711

872

872

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 8 COOLER

FRAME 8 CONDENSER

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/
CONDENSER

NIH, 1 Pass Cover, 150 psig

831

866

763

798

NIH, 2 Pass Cover, 150 psig

789

859

721

791

NIH, 3 Pass Cover, 150 psig

840

866

772

799

NIH/MWB End Cover, 150 psig

671

671

557

557

NIH, 1 Pass Cover, 300 psig

1220

1295

1086

1156

NIH, 2 Pass Cover, 300 psig

1177

1326

1029

1169

NIH, 3 Pass Cover, 300 psig

1224

1298

1096

1147

NIH/MWB End Cover, 300 psig

653

653

802

802

LEGEND

NIH

Nozzle-in-Head

MWB — Marine Waterbox

NOTE: Weight for NIH 2-Pass Cover, 150 psig is included in the heat exchanger weights shown in Table 6.

NOTE: If the cooler and condenser vessels must be sepa-
rated, the heat exchangers should be kept level by placing a
support plate under the tube sheets. The support plate will
also help to keep the vessels level and aligned when the ves-
sels are bolted back together.

NOTE: Wiring must also be disconnected. Label each wire
before removal (see Carrier Certified Prints). In order to dis-
connect the starter from the machine, remove wiring for the
oil pump, oil heater, control wiring at the power panel, and
the main motor leads at the starter lugs.

Remove all transducer and sensor wires at the sensor. Clip

all wire ties necessary to pull heat exchangers apart.

To Separate Cooler and Condenser:
1. Place a support plate under each tube sheet to keep each

vessel level (Fig. 6, Item 6).

2. Cut the refrigerant motor cooling line at the location shown

(Fig. 6, Item 7).

13

Advertising